Copper Pipe Size Chart (Type K, L, M and Metric)

Outside diameter, wall thickness, inside diameter and weight of copper water tube to ASTM B88, Types K, L and M, plus the common metric EN 1057 sizes. US copper tube is always 1/8 inch larger outside than its nominal size, so 1/2" copper is 5/8" (0.625 in) OD.

19 sizesChecked 2026-11-153 sources
Type Kt 1.65 mmt 0.065 in⌀22.23 mm⌀0.875 inType Lt 1.14 mmt 0.045 in⌀22.23 mm⌀0.875 inType Mt 0.81 mmt 0.032 in⌀22.23 mm⌀0.875 in3/4" pipet 2.87 mmt 0.113 in⌀26.67 mm⌀1.050 in
Same nominal 3/4", different tube: copper types share one OD and differ in wall; steel pipe of the same name is larger.Drawn to scale · Dimensions in mmDimensions in inches

Size chartTap a size for its drawing and full specs

19 of 19
SizeODOutside diametermminmm · intWall, Type Kmminmm · intWall, Type Lmminmm · intWall, Type Mmminmm · inIDInside diameter, Type Lmminmm · inWeight, Type Lkg/mlb/ftkg/m · lb/fttWall, EN 1057mminmm · in
ASTM B88: US copper water tube (nominal inch sizes)
1/4"9.530.3750.890.0350.760.030—80.3150.1880.126—
3/8"12.70.5001.250.0490.890.0350.640.02510.920.4300.2950.198—
1/2"15.880.6251.250.0491.020.0400.710.02813.840.5450.4240.285—
5/8"19.050.7501.250.0491.070.042—16.920.6660.5390.362—
3/4"22.230.8751.650.0651.140.0450.810.03219.940.7850.6770.455—
1"28.581.1251.650.0651.270.0500.890.03526.041.0250.9750.655—
1-1/4"34.931.3751.650.0651.40.0551.070.04232.131.2651.3160.884—
1-1/2"41.281.6251.830.0721.520.0601.250.04938.231.5051.6971.140—
2"53.982.1252.110.0831.780.0701.470.05850.421.9852.6041.750—
2-1/2"66.682.6252.410.0952.030.0801.650.06562.612.4653.6912.480—
3"79.383.1252.770.1092.290.0901.830.07274.82.9454.9563.330—
3-1/2"92.083.6253.050.1202.540.1002.110.083873.4256.3844.290—
4"104.784.1253.40.1342.790.1102.410.09599.193.9058.0065.380—
EN 1057: metric copper tube, half-hard (UK standard walls)
15 mm150.591—————0.70.028
22 mm220.866—————0.90.035
28 mm281.102—————0.90.035
35 mm351.378—————1.20.047
42 mm421.654—————1.20.047
54 mm542.126—————1.20.047

How copper tube is sized

US copper water tube (ASTM B88) is named by a nominal size that is neither the outside nor the inside diameter. The outside diameter is always the nominal size plus 1/8 inch: 1/2" tube = 0.625 in OD, 3/4" = 0.875 in, 1" = 1.125 in. All three types of one size share that OD, so they use the same fittings.

The type sets the wall: K is thickest, L medium, M thinnest. On a 3/4" tube that is 0.065, 0.045 and 0.032 in. Tube is marked by a colored stripe and printed text: green for K, blue for L, red for M (hard-drawn straight lengths).

Metric copper (EN 1057, used in Europe, the UK and much of the world) is named by its actual outside diameter in millimetres (15 mm tube is 15.0 mm outside), with the wall stated separately, e.g. 15 × 0.7. 15 mm is close to US 1/2" (15.9 mm) but not the same: fittings do not interchange without adapters.

About Copper Tube

Type L is the usual choice for interior water supply in the US and is required by many codes for underground or commercial work; Type M is common for residential supply and hydronic heating where allowed; Type K is used underground and for water services. Check the local plumbing code; requirements differ by state and city.

To identify a tube, measure the outside diameter with a caliper and subtract 1/8 inch for the nominal size. Then measure the wall at a cut end, or look at the stripe color. An OD of 0.875 in is 3/4" tube; a wall of about 0.045 in makes it Type L.

Copper tube and steel pipe with the same nominal size are different sizes: 3/4" copper is 0.875 in outside, 3/4" steel or PVC pipe is 1.050 in. They need transition fittings (sweat-to-thread adapters or dielectric unions).

ACR tube for air conditioning and refrigeration (ASTM B280) is named by its actual outside diameter, so 3/8" ACR is 0.375 in OD, the same tube as 1/4" nominal water tube. ACR is cleaned, capped and usually nitrogen-charged. Do not mix the two naming systems when ordering fittings.

Weights and water content

Weights are the ASTM B88 nominal weights per foot of straight tube; they follow from the dimensions and copper's density of 0.323 lb/in³ (8.94 g/cm³). Metric masses are computed from the stated dimensions with 8.9 g/cm³. Water volume per length follows from the inside diameter: 3/4" Type L holds about 0.025 US gal per foot (0.31 L/m).

Questions

What is the outside diameter of 1/2 inch copper pipe?

0.625 in (5/8", 15.9 mm) for Types K, L and M alike. US copper water tube is always 1/8 inch larger outside than its nominal size.

What is the difference between Type L and Type M copper?

Wall thickness. Type L is thicker than Type M: for 3/4" tube 0.045 in vs 0.032 in, which gives 0.455 vs 0.328 lb/ft. The outside diameter is the same, so both use the same fittings. Type L has a blue stripe, Type M red.

Is 15 mm copper the same as 1/2 inch?

No. 15 mm metric tube is 15.0 mm outside; US 1/2" tube is 15.9 mm (0.625 in). Push-fit fittings sometimes accept both, but compression and solder fittings need adapters.

Is 3/4 copper pipe the same size as 3/4 PVC pipe?

No. 3/4" copper tube is 0.875 in outside; 3/4" PVC and steel pipe are 1.050 in outside. Use a transition fitting.

What does the stripe color on copper pipe mean?

Green = Type K, blue = Type L, red = Type M, yellow = DWV (drain, waste and vent, thinner still). The color is on hard-drawn straight lengths; soft coils are marked by printed text.

Sources

  1. ASTM B88: Standard Specification for Seamless Copper Water Tube
  2. Copper Development Association: The Copper Tube Handbook (Table 14.3, dimensions and weights)
  3. EN 1057:2006+A1:2010, Copper and copper alloys, seamless round copper tubes for water and gas in sanitary and heating applications

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.