3" IMC Conduit Dimensions & Fill

Conduit Sizes · IMC: intermediate metal conduit

3" IMC conduit has a nominal inside diameter of 3.176 in (80.7 mm) and a total inside area of 7.922 in² (5,111 mm²). NEC Chapter 9 allows 3.169 in² (2045 mm²) for three or more conductors (40 %), 2.456 in² (1585 mm²) for two and 4.199 in² (2709 mm²) for one.

IDInside diameter (nominal)
80.7 mm3.176 in3.176 in80.7 mm
ODOutside diameter
88.3 mm3.476 in3.476 in88.3 mm
A₄₀Fill area, over 2 wires (40 %)
2045 mm²3.169 in²3.169 in²2045 mm²

Drawing

40 % fill areaID ⌀80.7 mmID ⌀3.176 inOD ⌀88.3 mmOD ⌀3.476 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

3" IMC specifications

Metric designator78
ODOutside diameter3.476 in88.3 mm
IDInside diameter (nominal)3.176 in80.7 mm
ATotal inside area (100 %)7.922 in²5,111 mm²
A₄₀Fill area, over 2 wires (40 %)3.169 in²2045 mm²
A₃₁Fill area, 2 wires (31 %)2.456 in²1585 mm²
A₅₃Fill area, 1 wire (53 %)4.199 in²2709 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.