3" PVC Sch 80 Conduit Dimensions & Fill
Conduit Sizes · PVC Schedule 80
3" PVC Sch 80 conduit has a nominal inside diameter of 2.864 in (72.7 mm) and a total inside area of 6.442 in² (4,156 mm²). NEC Chapter 9 allows 2.577 in² (1663 mm²) for three or more conductors (40 %), 1.997 in² (1288 mm²) for two and 3.414 in² (2203 mm²) for one.
- IDInside diameter (nominal)
- 72.7 mm2.864 in2.864 in72.7 mm
- ODOutside diameter
- 88.9 mm3.500 in3.500 in88.9 mm
- A₄₀Fill area, over 2 wires (40 %)
- 1663 mm²2.577 in²2.577 in²1663 mm²
Drawing
3" PVC Sch 80 specifications
| Metric designator | 78 |
|---|---|
| ODOutside diameter | 3.500 in88.9 mm |
| IDInside diameter (nominal) | 2.864 in72.7 mm |
| ATotal inside area (100 %) | 6.442 in²4,156 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 2.577 in²1663 mm² |
| A₃₁Fill area, 2 wires (31 %) | 1.997 in²1288 mm² |
| A₅₃Fill area, 1 wire (53 %) | 3.414 in²2203 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.