3" PVC Sch 80 Conduit Dimensions & Fill

Conduit Sizes · PVC Schedule 80

3" PVC Sch 80 conduit has a nominal inside diameter of 2.864 in (72.7 mm) and a total inside area of 6.442 in² (4,156 mm²). NEC Chapter 9 allows 2.577 in² (1663 mm²) for three or more conductors (40 %), 1.997 in² (1288 mm²) for two and 3.414 in² (2203 mm²) for one.

IDInside diameter (nominal)
72.7 mm2.864 in2.864 in72.7 mm
ODOutside diameter
88.9 mm3.500 in3.500 in88.9 mm
A₄₀Fill area, over 2 wires (40 %)
1663 mm²2.577 in²2.577 in²1663 mm²

Drawing

40 % fill areaID ⌀72.7 mmID ⌀2.864 inOD ⌀88.9 mmOD ⌀3.500 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

3" PVC Sch 80 specifications

Metric designator78
ODOutside diameter3.500 in88.9 mm
IDInside diameter (nominal)2.864 in72.7 mm
ATotal inside area (100 %)6.442 in²4,156 mm²
A₄₀Fill area, over 2 wires (40 %)2.577 in²1663 mm²
A₃₁Fill area, 2 wires (31 %)1.997 in²1288 mm²
A₅₃Fill area, 1 wire (53 %)3.414 in²2203 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.