3" RMC Conduit Dimensions & Fill
Conduit Sizes · RMC: rigid metal conduit (GRC)
3" RMC conduit has a nominal inside diameter of 3.090 in (78.5 mm) and a total inside area of 7.499 in² (4,838 mm²). NEC Chapter 9 allows 3.000 in² (1935 mm²) for three or more conductors (40 %), 2.325 in² (1500 mm²) for two and 3.974 in² (2564 mm²) for one.
- IDInside diameter (nominal)
- 78.5 mm3.090 in3.090 in78.5 mm
- ODOutside diameter
- 88.9 mm3.500 in3.500 in88.9 mm
- A₄₀Fill area, over 2 wires (40 %)
- 1935 mm²3.000 in²3.000 in²1935 mm²
Drawing
3" RMC specifications
| Metric designator | 78 |
|---|---|
| ODOutside diameter | 3.500 in88.9 mm |
| IDInside diameter (nominal) | 3.090 in78.5 mm |
| ATotal inside area (100 %) | 7.499 in²4,838 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 3.000 in²1935 mm² |
| A₃₁Fill area, 2 wires (31 %) | 2.325 in²1500 mm² |
| A₅₃Fill area, 1 wire (53 %) | 3.974 in²2564 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.