3" RMC Conduit Dimensions & Fill

Conduit Sizes · RMC: rigid metal conduit (GRC)

3" RMC conduit has a nominal inside diameter of 3.090 in (78.5 mm) and a total inside area of 7.499 in² (4,838 mm²). NEC Chapter 9 allows 3.000 in² (1935 mm²) for three or more conductors (40 %), 2.325 in² (1500 mm²) for two and 3.974 in² (2564 mm²) for one.

IDInside diameter (nominal)
78.5 mm3.090 in3.090 in78.5 mm
ODOutside diameter
88.9 mm3.500 in3.500 in88.9 mm
A₄₀Fill area, over 2 wires (40 %)
1935 mm²3.000 in²3.000 in²1935 mm²

Drawing

40 % fill areaID ⌀78.5 mmID ⌀3.090 inOD ⌀88.9 mmOD ⌀3.500 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

3" RMC specifications

Metric designator78
ODOutside diameter3.500 in88.9 mm
IDInside diameter (nominal)3.090 in78.5 mm
ATotal inside area (100 %)7.499 in²4,838 mm²
A₄₀Fill area, over 2 wires (40 %)3.000 in²1935 mm²
A₃₁Fill area, 2 wires (31 %)2.325 in²1500 mm²
A₅₃Fill area, 1 wire (53 %)3.974 in²2564 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.