3/4" PVC Sch 80 conduit has a nominal inside diameter of 0.722 in (18.3 mm) and a total inside area of 0.409 in² (264 mm²). NEC Chapter 9 allows 0.164 in² (106 mm²) for three or more conductors (40 %), 0.127 in² (82 mm²) for two and 0.217 in² (140 mm²) for one.

IDInside diameter (nominal)
18.3 mm0.722 in0.722 in18.3 mm
ODOutside diameter
26.7 mm1.050 in1.050 in26.7 mm
A₄₀Fill area, over 2 wires (40 %)
106 mm²0.164 in²0.164 in²106 mm²

Drawing

40 % fill areaID ⌀18.3 mmID ⌀0.722 inOD ⌀26.7 mmOD ⌀1.050 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

3/4" PVC Sch 80 specifications

Metric designator21
ODOutside diameter1.050 in26.7 mm
IDInside diameter (nominal)0.722 in18.3 mm
ATotal inside area (100 %)0.409 in²264 mm²
A₄₀Fill area, over 2 wires (40 %)0.164 in²106 mm²
A₃₁Fill area, 2 wires (31 %)0.127 in²82 mm²
A₅₃Fill area, 1 wire (53 %)0.217 in²140 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data