3/4" RMC Conduit Dimensions & Fill

Conduit Sizes · RMC: rigid metal conduit (GRC)

3/4" RMC conduit has a nominal inside diameter of 0.836 in (21.2 mm) and a total inside area of 0.549 in² (354 mm²). NEC Chapter 9 allows 0.220 in² (142 mm²) for three or more conductors (40 %), 0.170 in² (110 mm²) for two and 0.291 in² (188 mm²) for one.

IDInside diameter (nominal)
21.2 mm0.836 in0.836 in21.2 mm
ODOutside diameter
26.7 mm1.050 in1.050 in26.7 mm
A₄₀Fill area, over 2 wires (40 %)
142 mm²0.220 in²0.220 in²142 mm²

Drawing

40 % fill areaID ⌀21.2 mmID ⌀0.836 inOD ⌀26.7 mmOD ⌀1.050 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

3/4" RMC specifications

Metric designator21
ODOutside diameter1.050 in26.7 mm
IDInside diameter (nominal)0.836 in21.2 mm
ATotal inside area (100 %)0.549 in²354 mm²
A₄₀Fill area, over 2 wires (40 %)0.220 in²142 mm²
A₃₁Fill area, 2 wires (31 %)0.170 in²110 mm²
A₅₃Fill area, 1 wire (53 %)0.291 in²188 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.