1/2" RMC Conduit Dimensions & Fill
Conduit Sizes · RMC: rigid metal conduit (GRC)
1/2" RMC conduit has a nominal inside diameter of 0.632 in (16.1 mm) and a total inside area of 0.314 in² (203 mm²). NEC Chapter 9 allows 0.126 in² (81 mm²) for three or more conductors (40 %), 0.097 in² (63 mm²) for two and 0.166 in² (107 mm²) for one.
- IDInside diameter (nominal)
- 16.1 mm0.632 in0.632 in16.1 mm
- ODOutside diameter
- 21.3 mm0.840 in0.840 in21.3 mm
- A₄₀Fill area, over 2 wires (40 %)
- 81 mm²0.126 in²0.126 in²81 mm²
Drawing
1/2" RMC specifications
| Metric designator | 16 |
|---|---|
| ODOutside diameter | 0.840 in21.3 mm |
| IDInside diameter (nominal) | 0.632 in16.1 mm |
| ATotal inside area (100 %) | 0.314 in²203 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 0.126 in²81 mm² |
| A₃₁Fill area, 2 wires (31 %) | 0.097 in²63 mm² |
| A₅₃Fill area, 1 wire (53 %) | 0.166 in²107 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.