1/2" RMC Conduit Dimensions & Fill

Conduit Sizes · RMC: rigid metal conduit (GRC)

1/2" RMC conduit has a nominal inside diameter of 0.632 in (16.1 mm) and a total inside area of 0.314 in² (203 mm²). NEC Chapter 9 allows 0.126 in² (81 mm²) for three or more conductors (40 %), 0.097 in² (63 mm²) for two and 0.166 in² (107 mm²) for one.

IDInside diameter (nominal)
16.1 mm0.632 in0.632 in16.1 mm
ODOutside diameter
21.3 mm0.840 in0.840 in21.3 mm
A₄₀Fill area, over 2 wires (40 %)
81 mm²0.126 in²0.126 in²81 mm²

Drawing

40 % fill areaID ⌀16.1 mmID ⌀0.632 inOD ⌀21.3 mmOD ⌀0.840 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

1/2" RMC specifications

Metric designator16
ODOutside diameter0.840 in21.3 mm
IDInside diameter (nominal)0.632 in16.1 mm
ATotal inside area (100 %)0.314 in²203 mm²
A₄₀Fill area, over 2 wires (40 %)0.126 in²81 mm²
A₃₁Fill area, 2 wires (31 %)0.097 in²63 mm²
A₅₃Fill area, 1 wire (53 %)0.166 in²107 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.