DIN Rail Sizes: TS35 × 7.5, TS35 × 15, TS15, G32 and Module Widths
The rail almost everyone means is TS35: a 35 mm wide top-hat rail, either 7.5 mm or 15 mm deep (IEC 60715). Devices clip onto the 35 mm flanges and are sized in 17.5 mm modules (DIN 43880), so a 12-module row needs 210 mm of rail.
Rail typesWidth across the flanges × depth
| Rail | WWidthmmin | HHeightmmin | Standard | Typical use |
|---|---|---|---|---|
| TS35 × 7.5 (top hat) | 351.378 | 7.50.295 | IEC 60715 (EN 50022) | Standard rail for MCBs, RCDs, terminals, relays, PLCs, power supplies |
| TS35 × 15 (deep top hat) | 351.378 | 150.591 | IEC 60715 (EN 50022) | Heavier devices, long unsupported spans, cable routing behind the rail |
| TS15 (miniature) | 150.591 | 5.50.217 | IEC 60715 (EN 50045) | Small terminals and devices in tight spaces |
| G32 (G-section) | 321.260 | — | IEC 60715 (EN 50035, withdrawn) | Older heavy terminals; asymmetric, so devices hook on one side |
No exact match. The nearest sizes:
How to identify a rail
Measure the width across the flanges, the edges the devices hook onto. 35 mm: TS35. 15 mm: TS15. 32 mm with one deep and one shallow lip: G32 (G-section).
Then the depth from the flange to the back of the rail: 7.5 mm or 15 mm for TS35. Devices fit both; the 15 mm rail is stiffer and leaves room for wires behind it.
Designations: "TS 35 × 7.5" (Weidmüller, Siemens), "NS 35/7.5" (Phoenix Contact), "EN 50022" (old standard number) all mean the same rail. EN 50022, EN 50045 and EN 50035 were replaced by IEC/EN 60715.
Perforation (slots in the crown for mounting screws) is not standardized: slot size and spacing differ by maker. Unperforated rail is stiffer and is drilled where needed.
About DIN Rail
DIN rail lets breakers, terminals, relays, timers, power supplies and PLCs from any manufacturer share one mounting system. The rail is screwed to the back plate of the enclosure; devices hook on the top flange and snap over the bottom one with a spring clip, released with a screwdriver.
Rails are galvanized or zinc-passivated steel as standard; aluminium is lighter, stainless steel resists corrosion, and copper rails double as an earth bar.
Modular installation devices (MCBs, RCDs, contactors for distribution boards) follow DIN 43880: a 45 mm front that projects through the cover cut-out and a width in modules. The module pitch is 17.5 mm in DIN 43880 and 18 mm in many catalogues (a 17.5 mm device plus tolerance); a single-pole MCB is one module, an RCBO usually one or two, a 4-pole RCCB four. When filling a whole row, check which pitch the enclosure and the devices use.
Module widths of common devices
| Device | Typical modules | Width |
|---|---|---|
| MCB 1-pole | 1 | 17.5 mm |
| MCB 1P+N / RCBO (compact) | 1 | 17.5 mm |
| RCBO 2-pole | 2 | 35 mm |
| MCB 3-pole | 3 | 52.5 mm |
| RCCB 2-pole | 2 | 35 mm |
| RCCB 4-pole | 4 | 70 mm |
| Surge protector 3P+N | 4 | 70 mm |
| Modular contactor 25 A 4-pole | 2 | 35 mm |
| kWh meter, single phase | 1–4 | 17.5–70 mm |
Panel sizes in modules
Consumer units and distribution boards are sold by module count per row: 12, 18 and 24 modules are common in Europe (210, 315 and 420 mm of usable rail at 17.5 mm per module). Leave about 20 % spare modules for later circuits and for the heat of densely packed breakers.
Other rail types
C-section rails (C20, C30, C40, C50; formerly EN 50024) carry heavy terminal blocks and are common in older industrial panels. TS32 / G32 is the G-shaped rail of EN 50035, withdrawn but still found in installed equipment. Devices for G32 hook into the deeper lip first; many terminal blocks clip on both TS35 and G32.
Questions
What is the standard DIN rail size?
TS35 × 7.5: 35 mm wide, 7.5 mm deep, standardized in IEC/EN 60715 (formerly EN 50022). The 15 mm deep version is used for heavier devices.
How wide is one DIN rail module?
One module: 17.5 mm in DIN 43880, quoted as 18 mm by many manufacturers. A 1-pole MCB is one module wide; a 4-pole RCD four modules (70–72 mm).
Do devices fit both 7.5 mm and 15 mm deep TS35 rail?
Yes. Both have the same 35 mm flange width and lip; only the depth behind the flanges differs. The device sits 7.5 mm further forward on the 15 mm rail, which can matter behind a cover cut-out.
How do I cut DIN rail?
With a hacksaw and a deburring file, or a rail cutter (punch-type tools cut perforated and unperforated rail cleanly without bending). Leave the cut ends free of burrs so clips slide on.
What is the difference between a top hat and a G rail?
Top hat (TS35, TS15) is symmetric: devices clip on either way up. G rail (G32) is asymmetric with one deep and one shallow lip, so devices hook into the deep side first and always mount the same way.
Sources
- IEC 60715:2017, Dimensions of low-voltage switchgear and controlgear: standardized mounting on rails
- DIN 43880: Built-in equipment for electrical installations: overall dimensions and related mounting dimensions
- Phoenix Contact: NS 35/7.5, NS 35/15, NS 15, NS 32 DIN rail drawings
- Weidmüller: TS 35, TS 15, TS 32 mounting rails catalogue
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.