Electrical Box Sizes and Box Fill Chart: NEC 314.16, EU and UK Boxes

Box fill is counted in volume: each 14 AWG conductor needs 2.00 in³, each 12 AWG 2.25 in³, a switch or receptacle counts as two conductors, and all grounds together as one. A 4 × 2-1/8 in square box (30.3 in³) therefore holds fifteen 14 AWG or thirteen 12 AWG conductors with nothing else in it.

24 box sizesChecked 2026-11-155 sources

Box volumes and maximum conductorsMaximum conductors of one size with nothing else in the box

24 of 24 boxes
Box (trade size)Volumecm³in³Max 18 AWGMax 16 AWGMax 14 AWGMax 12 AWGMax 10 AWGMax 8 AWGMax 6 AWG
Round and octagonal
4 × 1-1/4 in round/octagonal20512.58765542
4 × 1-1/2 in round/octagonal25415.510876653
4 × 2-1/8 in round/octagonal35221.51412109874
Square
4 × 1-1/4 in square29518.0121098763
4 × 1-1/2 in square34421.01412109874
4 × 2-1/8 in square49730.32017151312106
4-11/16 × 1-1/4 in square41825.5171412111085
4-11/16 × 1-1/2 in square48329.5191614131195
4-11/16 × 2-1/8 in square68842.02824211816148
Device (single gang) and handy boxes
3 × 2 × 1-1/2 in device1237.55433321
3 × 2 × 2 in device16410.06554432
3 × 2 × 2-1/4 in device17210.57654432
3 × 2 × 2-1/2 in device20512.58765542
3 × 2 × 2-3/4 in device22914.09876542
3 × 2 × 3-1/2 in device29518.0121098763
4 × 2-1/8 × 1-1/2 in device16910.36554432
4 × 2-1/8 × 1-7/8 in device21313.08765542
4 × 2-1/8 × 2-1/8 in device23814.59876542
Masonry boxes
3-3/4 × 2 × 2-1/2 in masonry22914.09876542
3-3/4 × 2 × 3-1/2 in masonry34421.01412109874
FS and FD cast boxes
FS, minimum 1-3/4 in deep, single cover/gang22113.59766542
FD, minimum 2-3/8 in deep, single cover/gang29518.0121098763
FS, minimum 1-3/4 in deep, multiple cover/gang29518.0121098763
FD, minimum 2-3/8 in deep, multiple cover/gang39324.016131210984

How to count box fill (NEC 314.16(B))

Conductors: each insulated conductor that enters the box and is spliced or connected counts once, at its own size. A conductor that passes through unbroken counts once (twice if it is looped 12 in or more for a device). Pigtails that start and end inside the box do not count.

Devices: each yoke or strap (switch, receptacle, dimmer) counts as two conductors of the largest size connected to it, or four for a device wider than 2 in that needs two gangs.

Grounds: all equipment grounding conductors together count as one conductor of the largest ground size (plus one quarter allowance for each extra set of isolated grounds).

Clamps and fittings: internal cable clamps, however many, count as one conductor of the largest size; each fixture stud or hickey counts as one.

Volumes per conductor (Table 314.16(B)): 18 AWG 1.50, 16 AWG 1.75, 14 AWG 2.00, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00, 6 AWG 5.00 in³. Add up the allowances; the box (plus any plaster ring, extension ring or domed cover marked with its volume) must be at least that big.

About Electrical Boxes

The table lists the standard metal boxes of NEC Table 314.16(A) with their volumes. The "Max" columns are the number of conductors of one size that fit when there is nothing else in the box: the volume divided by the allowance and rounded down, which is how the NEC table is built. As soon as a device, ground or clamp is in the box, use the calculator.

Plastic (nonmetallic) boxes and any box marked with its volume are rated by the marked volume, not by the table (314.16(A)(2)). Typical single-gang plastic boxes are 18 to 22.5 in³, two-gang 32 to 35 in³, three-gang about 45–55 in³, and round ceiling boxes 15–22 in³. Read the stamp inside the box.

Plaster rings, extension rings and raised covers add their marked volume. A 4 in square box with a 1/2 in raised single-device ring is a common way to gain the few cubic inches needed for a GFCI receptacle, which is bulky but still counts only as two conductors.

Fill is not the only limit: conductors 4 AWG and larger fall under the pull-box rules of 314.28 (straight pulls 8 × the largest raceway, angle pulls 6 ×), and boxes over 100 in³ follow 314.16(A)(1) by calculation.

Volume allowance per conductor (Table 314.16(B))

Conductorin³cm³
18 AWG1.5024.6
16 AWG1.7528.7
14 AWG2.0032.8
12 AWG2.2536.9
10 AWG2.5041.0
8 AWG3.0049.2
6 AWG5.0081.9

Worked example

Single-gang box with one receptacle, two 12/2 NM cables (in and out): 4 insulated conductors × 2.25 = 9.0 in³; receptacle 2 × 2.25 = 4.5 in³; grounds 1 × 2.25 = 2.25 in³; box with internal clamps + 2.25 in³. Total 18.0 in³ → a 3 × 2 × 3-1/2 in metal device box (18.0 in³) or a plastic box marked 18 in³ or more. Without internal clamps 15.75 in³ is needed.

European flush boxes

Continental Europe uses round flush-mounting boxes (DIN 49073-1, EN 60670): 60 mm inside diameter with device fixing screws 60 mm apart, set into a 68 mm hole. Common depths are about 40 mm (standard) and 60–65 mm (deep, for electronics or many wires). Multi-gang boxes link on 71 mm centres, matching the frame pitch of most switch ranges. Devices are fixed by screws on 60 mm centres or by claws.

UK back boxes

UK accessories (BS 1363 sockets, switches) fit square back boxes to BS 4662 / BS EN 60670 with 60.3 mm fixing centres (M3.5 screws) for single 86 × 86 mm plates. Standard depths: 16 mm (shallow, switches only, often dry-lining), 25 mm (switches, slim sockets), 35 mm (sockets, the usual choice) and 47 mm (sockets with USB, fused spurs, many cables). Twin-socket boxes are about 146 mm wide with fixing centres 120.6 mm apart.

DepthTypical use
16 mmLight switches on plasterboard
25 mmLight switches, slim plates
35 mmSockets, fused connection units
47 mmUSB sockets, smart switches, crowded boxes

Questions

How many wires can go in a 4 inch square box?

A 4 × 1-1/2 in square box (21.0 in³) holds ten 14 AWG or nine 12 AWG conductors with nothing else; the deep 4 × 2-1/8 in (30.3 in³) holds fifteen 14 AWG or thirteen 12 AWG. Subtract two conductors per device, one for all grounds and one for internal clamps.

How many cubic inches is a single gang box?

Metal 3 × 2 in device boxes range from 7.5 in³ (1-1/2 in deep) to 18.0 in³ (3-1/2 in deep). Plastic single-gang boxes are usually marked 18–22.5 in³.

Do ground wires count in box fill?

Yes, but all of them together count as one conductor of the largest ground size (NEC 314.16(B)(5)). Each additional set of isolated equipment grounds adds a quarter allowance.

Does a wire nut or pigtail count in box fill?

No. Wire connectors are not counted, and a pigtail that starts and ends in the box is not counted either. The conductors entering the box are.

How deep is a UK socket back box?

35 mm for a standard socket; 47 mm for sockets with built-in USB chargers or where several cables enter. 25 mm boxes suit switches and slim sockets only.

Sources

  1. NFPA 70 (NEC) 2023: 314.16 Number of conductors in outlet, device and junction boxes; Tables 314.16(A) and 314.16(B)
  2. Electrical Contractor: Box-fill calculations: understanding NEC Article 314 (series)
  3. Mike Holt: NEC requirements for sizing outlet boxes
  4. BS 4662 / BS EN 60670: boxes for flush mounting (UK back boxes)
  5. DIN 49073-1: Installation boxes for flush mounting (60 mm screw spacing)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.