IP Rating Chart: IEC 60529 Codes and NEMA Enclosure Types
An IP code has two digits: the first (0–6) rates protection against solid objects and dust, the second (0–9) against water. IP67 means dust-tight (6) and survives immersion to 1 m for 30 minutes (7). An X replaces a digit that was not tested: IPX7 is waterproof to 1 m but has no dust rating.
Common IP codesTap a code for what it means and how it is tested
| Code | Solids and dust | Water | Typical use |
|---|---|---|---|
| Both digits rated | |||
| IP20 | Objects ≥ 12.5 mm (finger) | No protection | Indoor electrical enclosures, finger-safe terminals, DIN-rail devices in a cabinet |
| IP21 | Objects ≥ 12.5 mm (finger) | Vertically dripping water | Indoor equipment that may see condensation drips |
| IP22 | Objects ≥ 12.5 mm (finger) | Dripping water with enclosure tilted up to 15° | Indoor equipment protected against dripping water when tilted |
| IP23 | Objects ≥ 12.5 mm (finger) | Spraying water up to 60° from vertical | Equipment that may see light rain or spray, under cover |
| IP40 | Objects ≥ 1.0 mm (wire, screws) | No protection | Indoor enclosures where small wires or tools must not get in |
| IP44 | Objects ≥ 1.0 mm (wire, screws) | Splashing water from any direction | Bathroom zone 2 fittings, splash-proof sockets, outdoor lights under eaves, IEC 60309 sockets |
| IP54 | Dust-protected (limited ingress, no harmful deposit) | Splashing water from any direction | Dusty indoor areas and sheltered outdoor equipment |
| IP55 | Dust-protected (limited ingress, no harmful deposit) | Water jets, 6.3 mm nozzle, 12.5 L/min | Outdoor equipment and machines that are hosed down lightly |
| IP65 | Dust-tight (no ingress, tested under vacuum) | Water jets, 6.3 mm nozzle, 12.5 L/min | Outdoor lights and enclosures exposed to rain and jets; dust-tight |
| IP66 | Dust-tight (no ingress, tested under vacuum) | Powerful water jets, 12.5 mm nozzle, 100 L/min | Outdoor and marine equipment exposed to heavy seas or powerful jets |
| IP67 | Dust-tight (no ingress, tested under vacuum) | Temporary immersion, 15 cm to 1 m, 30 min | Phones, outdoor connectors, junction boxes: survives 30 min at 1 m |
| IP68 | Dust-tight (no ingress, tested under vacuum) | Continuous immersion beyond 1 m, conditions set by the manufacturer | Submersible lights, pool equipment, phones: depth and time stated by the maker |
| IP69 | Dust-tight (no ingress, tested under vacuum) | High-pressure, high-temperature water jets (80 °C) | Equipment cleaned with high-pressure hot water (IEC 60529 since 2013) |
| IP69K | Dust-tight (no ingress, tested under vacuum) | High-pressure steam-cleaning jets, 80 °C, 8–10 MPa, 14–16 L/min (ISO 20653) | Food processing and vehicle equipment cleaned with steam jets (ISO 20653) |
| IP6K9K | Dust-tight, tested with increased pressure difference (ISO 20653) | High-pressure steam-cleaning jets, 80 °C, 8–10 MPa, 14–16 L/min (ISO 20653) | Vehicle components cleaned with high-pressure steam (ISO 20653) |
| One digit not tested (X) | |||
| IPX4 | Not tested or not specified | Splashing water from any direction | Splash-resistant electronics, speakers, earbuds (dust not rated) |
| IPX5 | Not tested or not specified | Water jets, 6.3 mm nozzle, 12.5 L/min | Equipment tested against water jets only |
| IPX7 | Not tested or not specified | Temporary immersion, 15 cm to 1 m, 30 min | Watches, earbuds, phones rated for 1 m immersion (dust not rated) |
| IPX8 | Not tested or not specified | Continuous immersion beyond 1 m, conditions set by the manufacturer | Submersible devices, depth set by the maker (dust not rated) |
| IP5X | Dust-protected (limited ingress, no harmful deposit) | Not tested or not specified | Dust-protected, water not rated |
| IP6X | Dust-tight (no ingress, tested under vacuum) | Not tested or not specified | Dust-tight, water not rated |
No exact match. The nearest sizes:
How to read an IP code
IP = Ingress Protection, IEC 60529. First digit 0–6: solid objects and dust. 1–4 are probe tests (a 50 mm ball, a 12.5 mm finger, a 2.5 mm and a 1.0 mm rod must not get in); 5 is dust-protected, 6 dust-tight.
Second digit 0–9: water. 1–4 drip, spray and splash tests; 5 and 6 water jets; 7 and 8 immersion; 9 high-pressure hot water. The scale is not cumulative above 6: an IP67 device has not necessarily passed the jet tests of 5 and 6. Products that pass both are marked with both codes, e.g. IP66/IP67.
X stands for a digit that was not tested. IPX7 says nothing about dust; it does not mean "no protection".
Optional letters. An additional letter A–D after the digits rates protection of people against access to hazardous parts (back of hand, finger, tool, wire) when the first digit is lower. Supplementary letters: H high-voltage apparatus, M/S tested while moving/stationary, W weather conditions.
K suffix (6K, 9K, also 4K, 5K) comes from ISO 20653 for road vehicles: tests at higher pressure. IP69K is the steam-jet washdown rating used for food machinery and trucks.
About IP Ratings
IP codes are the international way to state how well an enclosure keeps out fingers, dust and water. They apply to electrical enclosures, luminaires, connectors, phones and watches alike, and they are tested, not estimated: each digit corresponds to a defined test in IEC 60529.
For indoor electrical work IP20 (finger-safe) is the baseline for anything inside a cabinet. Bathrooms and kitchens call for IP44 close to water (IEC 60364-7-701 zone 2 needs at least IPX4). Outdoors, IP65 handles rain and hosing, IP66 heavy seas and pressure washers at a distance, and IP67/IP68 temporary or continuous immersion.
IPX8 and IP68 have no fixed depth: the manufacturer states it ("IP68 to 3 m for 2 h"). Consumer phones rated IP68 are usually tested in fresh still water; salt water, soap and hot water are outside the test. A rating is also only as good as its gaskets and cable glands: an IP67 box with an unrated gland is not IP67.
North American specifications usually call for NEMA 250 enclosure types instead. NEMA types also cover corrosion, icing and oil, which IP codes do not, so a NEMA type can be converted to a minimum IP code but not the other way round.
First digit: solids
| Digit | Protection | Test |
|---|---|---|
| 0 | None | — |
| 1 | Objects ≥ 50 mm | 50 mm sphere must not fully enter |
| 2 | Objects ≥ 12.5 mm (fingers) | 12.5 mm sphere; jointed test finger 80 mm long |
| 3 | Objects ≥ 2.5 mm | 2.5 mm rod must not enter |
| 4 | Objects ≥ 1.0 mm | 1.0 mm wire must not enter |
| 5 | Dust-protected | Talc dust chamber; ingress allowed if it does not interfere |
| 6 | Dust-tight | Talc dust chamber with vacuum, 8 h; no ingress |
Second digit: water
| Digit | Protection | Test (summary) |
|---|---|---|
| 0 | None | — |
| 1 | Vertically dripping water | 1 mm/min, 10 min |
| 2 | Dripping, tilted 15° | 3 mm/min, 2.5 min in each of 4 tilt positions |
| 3 | Spraying water | Up to 60° from vertical, 10 L/min, 5 min |
| 4 | Splashing water | All directions, 10 L/min, 5 min |
| 5 | Water jets | 6.3 mm nozzle, 12.5 L/min, 3 m, at least 3 min |
| 6 | Powerful water jets | 12.5 mm nozzle, 100 L/min, 3 m, at least 3 min |
| 6K | Powerful jets, increased pressure (ISO 20653) | 6.3 mm nozzle, 75 L/min, 1000 kPa, 3 m, 3 min |
| 7 | Temporary immersion | 15 cm to 1 m (bottom 1 m), 30 min |
| 8 | Continuous immersion | Beyond 1 m; depth and time agreed, must be harsher than 7 |
| 9 | High-pressure, high-temperature jets | 80 °C water, 8–10 MPa, 14–16 L/min (IEC 60529 A2) |
| 9K | Steam-cleaning jets (ISO 20653) | 80 °C, 8–10 MPa, 14–16 L/min, 10–15 cm, 0°/30°/60°/90°, 30 s each |
NEMA 250 enclosure types and IP equivalents
NEMA's own comparison: a NEMA type meets at least the IP code shown. The conversion works one way only, because NEMA types add tests (corrosion, ice, oil, gasket ageing) that IP codes do not have.
| NEMA type | Location | Protects against | ≥ IP |
|---|---|---|---|
| 1 | Indoor | Contact with live parts, falling dirt | IP10 |
| 2 | Indoor | Type 1 + dripping and light splashing water | IP11 |
| 3 | Outdoor | Rain, sleet, snow, windblown dust; undamaged by ice | IP54 |
| 3R | Outdoor | Rain, sleet, snow; undamaged by ice (no dust) | IP14 |
| 3S | Outdoor | Type 3 + mechanisms operable when iced | IP54 |
| 3X, 3RX, 3SX | Outdoor | As 3, 3R, 3S + corrosion | — |
| 4 | Indoor/outdoor | Windblown dust, rain, hose-directed water | IP66 |
| 4X | Indoor/outdoor | Type 4 + corrosion (stainless, polycarbonate) | IP66 |
| 5 | Indoor | Settling dust, lint, dripping water | IP52 |
| 6 | Indoor/outdoor | Temporary submersion at limited depth | IP67 |
| 6P | Indoor/outdoor | Prolonged submersion + corrosion | IP68 |
| 7, 8, 9, 10 | Hazardous | Explosion-proof / dust-ignition-proof / mining (NEC classified locations) | — |
| 12, 12K | Indoor | Circulating dust, lint, fibres, dripping non-corrosive liquids | IP52 |
| 13 | Indoor | Type 12 + spraying oil and coolant | IP54 |
Questions
What is the difference between IP67 and IP68?
IP67 is tested at up to 1 m depth for 30 minutes. IP68 means continuous immersion beyond 1 m under conditions the manufacturer states, for example 1.5 m or 6 m for 30 minutes. Both are dust-tight (6).
Is IP65 waterproof?
It resists rain and water jets (6.3 mm nozzle, 12.5 L/min from 3 m) from any direction, but it is not rated for immersion. For submersion you need IPX7 or IPX8.
What does the X in IPX4 mean?
The first digit was not tested. IPX4 means splash-proof from all directions with no dust rating; it does not mean the product has no protection against solids.
What IP rating do I need for a bathroom?
Under IEC 60364-7-701 (BS 7671 section 701), equipment in zone 1 (above the bath or shower up to 2.25 m) needs at least IPX4, and IPX5 where water jets are used for cleaning; zone 2 needs IPX4. Many manufacturers simply specify IP44 or IP65.
What is the IP equivalent of NEMA 4X?
At least IP66. NEMA 4X adds corrosion resistance, which has no IP equivalent, so an IP66 enclosure is not automatically NEMA 4X.
Is IP69K better than IP68?
They test different things. IP69K is for high-pressure, 80 °C steam-jet cleaning; IP68 is for long immersion. An enclosure can pass one and fail the other, which is why food-industry parts are often marked IP67/IP69K.
Sources
- IEC 60529:1989+A1:1999+A2:2013, Degrees of protection provided by enclosures (IP Code)
- ISO 20653: Road vehicles, Degrees of protection (IP code) (6K, 9K)
- NEMA 250: Enclosures for Electrical Equipment (1000 Volts Maximum)
- NEMA: A Brief Comparison of NEMA 250 and IEC 60529 (enclosure type to IP)
- Hammond Manufacturing: IP and NEMA enclosure ratings guide
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.