Circuit Breaker Chart: Trip Curves B, C, D, K, Z, Ratings and Types
The letter on a miniature circuit breaker gives the current at which it trips instantly, as a multiple of its rating In: B 3–5 ×, C 5–10 ×, D 10–20 × (IEC 60898-1). A C16 breaker therefore trips magnetically somewhere between 80 A and 160 A, and thermally (after minutes) above 1.45 × 16 A = 23 A.
Trip curves and device typesTrip curves in multiples of the rated current In; device types below
| Type | Instant trip (× In)× | No trip below (× In)× | Trips within 1 h at (× In)× | Standard | Trip sensitivity | Typical use | Protects |
|---|---|---|---|---|---|---|---|
| MCB trip characteristics | |||||||
| B curve | 3–5 | 1.13 | 1.45 | IEC 60898-1 | — | Resistive loads, lighting, domestic socket circuits, long cable runs (low fault current) | — |
| C curve | 5–10 | 1.13 | 1.45 | IEC 60898-1 | — | General commercial and industrial circuits, small motors, fluorescent and LED lighting with drivers | — |
| D curve | 10–20 | 1.13 | 1.45 | IEC 60898-1 | — | High inrush: transformers, motors started direct on line, welding sets, X-ray equipment | — |
| K curve | 8–15 (by maker) | 1.05 | 1.2 | IEC 60947-2 (maker curve) | — | Motors and transformers, with closer thermal protection than D | — |
| Z curve | 2–3 | 1.05 | 1.2 | IEC 60947-2 (maker curve) | — | Semiconductors, electronics, measuring and control circuits | — |
| Protective device types | |||||||
| MCB | — | — | — | IEC 60898-1 / IEC 60947-2 | Overload and short circuit only | — | Cables against overload and short circuit |
| RCCB / RCD | — | — | — | IEC 61008-1 | IΔn 10, 30, 100, 300, 500 mA | — | People (30 mA) or fire (100–300 mA) against earth leakage; no overcurrent protection |
| RCBO | — | — | — | IEC 61009-1 | IΔn usually 30 mA, plus B/C curve | — | RCD and MCB in one device, one per circuit |
| AFDD | — | — | — | IEC 62606 | Series and parallel arc detection | — | Fire caused by arcing faults in cables and connections |
| GFCI (Class A) | — | — | — | UL 943 | Trips at 6 mA max (4–6 mA) | — | People against shock: bathrooms, kitchens, garages, outdoors (NEC 210.8) |
| GFPE | — | — | — | UL 1053 / NEC 210.8, 426, 427 | Typically 30 mA | — | Equipment: heat tracing, de-icing, large services (not for personnel) |
| AFCI (combination) | — | — | — | UL 1699 | Series and parallel arc detection | — | Fire from arcing faults in dwelling branch circuits (NEC 210.12) |
| Dual-function AFCI/GFCI | — | — | — | UL 1699 + UL 943 | Arc detection + 4–6 mA ground fault | — | Kitchens and laundries that need both AFCI and GFCI |
| MCCB | — | — | — | IEC 60947-2 / UL 489 | Fixed or adjustable thermal-magnetic or electronic trip | — | Feeders and large loads, typically 16–1600 A |
No exact match. The nearest sizes:
How to read a breaker marking
C16 = C characteristic, rated current In = 16 A. The number is the current the breaker carries indefinitely at its reference temperature (30 °C for IEC 60898-1).
Thermal part. A bimetal opens the breaker on overload. Under IEC 60898-1 it must not trip within 1 hour at 1.13 × In and must trip within 1 hour at 1.45 × In; at 2.55 × In it trips in seconds to a minute.
Magnetic part. A coil trips instantly (under 0.1 s) on short circuit. The letter places that band: B 3–5 × In, C 5–10 × In, D 10–20 × In. The breaker may trip anywhere in the band; above it, it must trip instantly.
Breaking capacity, the number in a rectangle (e.g. 6000 or 10000), is the largest fault current in amps the breaker can interrupt (Icn). Use at least the prospective fault current at the board: 6 kA is usual in European homes, 10 kA in commercial boards.
US breakers are marked with the rating only (15, 20, 30 A …) and an interrupting rating (10,000 AIC typical for residential, 22 kA and up for commercial). Their trip curves are defined by UL 489 and the manufacturer, not by B/C/D letters.
About Circuit Breakers
Choose the trip curve so that normal inrush does not trip the breaker, but a short circuit at the far end of the cable still reaches the instantaneous band. A B breaker trips at the lowest fault current, which helps on long runs where cable resistance limits the fault current; a D breaker rides through the inrush of a transformer or a large motor but needs a low-impedance circuit to trip fast on a fault.
For a final circuit, the rule of thumb is: domestic sockets and lighting B or C, commercial circuits and LED lighting with large driver inrush C, motors and transformers D (or K). Check the loop impedance: for a B16 the fault current must reach 5 × 16 = 80 A, so at 230 V the earth-fault loop impedance may be at most 230 / 80 ≈ 2.9 Ω (BS 7671 tables apply a 0.95 factor and give 2.73 Ω).
Residual-current devices measure the difference between line and neutral current. A 30 mA RCD (or a 4–6 mA GFCI in North America) protects people from shock; 100–300 mA devices protect against fire. An RCD alone does not protect against overload. It must be paired with an MCB or fuse, or replaced by an RCBO that does both.
Arc-fault devices (AFCI in the US, AFDD in IEC countries) look for the current signature of arcing in damaged cords and loose terminals. They are required in most US dwelling branch circuits (NEC 210.12) and in some IEC countries for bedrooms and high-risk locations.
Standard current ratings
| System | Ratings |
|---|---|
| IEC MCB (preferred, IEC 60898-1) | 6, 10, 13, 16, 20, 25, 32, 40, 50, 63 A (also 0.5–4 A, 80, 100, 125 A) |
| US standard ratings (NEC 240.6(A)) | 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400 A and up |
| US residential plug-on breakers | 15, 20, 30, 40, 50, 60 A common; 70–125 A two-pole; 100–200 A mains |
Widths: DIN modules and US plug-on breakers
IEC modular devices are sized in modules of 17.5 mm (DIN 43880); a single-pole MCB is 1 module, a 2-pole RCBO usually 2, a 4-pole RCCB 4. Some ranges are built on an 18 mm module (e.g. 9 mm half-module systems), so a row of 12 of them is 6 mm wider than 12 × 17.5 mm. Panel sizes are quoted in modules: a "12-module" row needs 12 × 17.5 = 210 mm of rail.
US load centers take plug-on breakers sized per pole. Square D QO and Eaton CH breakers are 3/4 in wide; Square D Homeline, Eaton BR, Siemens QP and GE THQL are 1 in wide. Tandem (twin, "half-size") breakers put two 1/2 in circuits in one 1 in space, only where the panel label allows them. Breakers of different brands are not interchangeable unless they are UL-classified for that panel.
| Family | Width per pole | Notes |
|---|---|---|
| IEC MCB (DIN rail) | 17.5 mm (1 module) | Some brands 18 mm |
| Square D QO | 3/4 in (19 mm) | Bolt-on QOB version exists |
| Eaton Cutler-Hammer CH | 3/4 in (19 mm) | |
| Square D Homeline | 1 in (25.4 mm) | Not interchangeable with QO |
| Eaton BR | 1 in (25.4 mm) | |
| Siemens QP | 1 in (25.4 mm) | |
| GE THQL | 1 in (25.4 mm) | |
| Tandem / twin breaker | 2 circuits in 1 in | Only in spaces the panel label allows |
RCD types and sensitivities
| Type | Detects | Use |
|---|---|---|
| AC | Sinusoidal AC residual current | Resistive loads only; restricted or banned in several countries |
| A | AC + pulsating DC | General use with electronic loads |
| F | Type A + mixed frequencies | Single-phase inverter drives, washing machines, heat pumps |
| B | Type F + smooth DC | Three-phase inverters, EV chargers without DC detection, PV |
| 10 mA | — | Extra protection (medical, special locations) |
| 30 mA | — | Personal protection: sockets, bathrooms, outdoor |
| 100 / 300 mA | — | Fire protection, upstream selectivity (type S, time delayed) |
Questions
What is the difference between a B and a C circuit breaker?
The instantaneous trip level. A B breaker trips instantly between 3 and 5 times its rating, a C breaker between 5 and 10 times. Both have the same overload (thermal) behaviour. A B16 trips instantly at 48–80 A, a C16 at 80–160 A, so C rides through higher inrush but needs a lower loop impedance.
When should I use a D curve breaker?
For loads with inrush of 10–20 times their running current: transformers, welding sets, motors started direct on line, some UPS and X-ray equipment. Check that the circuit's fault current exceeds 20 × In, otherwise the breaker may not trip instantly on a fault.
What is the trip current of a 30 mA RCD?
It must trip at or below 30 mA residual current (typically it trips at 15–30 mA), within 300 ms at 30 mA and 40 ms at 150 mA for a general type. A US GFCI (UL 943 Class A) trips at 4–6 mA.
How wide is a DIN rail circuit breaker?
One module, 17.5 mm per pole (DIN 43880); some manufacturers use 18 mm. A 2-pole breaker is 35 mm, a 4-pole RCCB 70 mm.
Can I put a Square D QO breaker in a Homeline panel?
No. QO breakers are 3/4 in wide and Homeline 1 in, with different bus connections. Use the breaker brand and type listed on the panel label, or a breaker UL-classified for that panel.
What is the difference between an RCD and an RCBO?
An RCD (RCCB) trips only on earth leakage and has no overload protection. An RCBO combines an RCD with an MCB in one device, so one fault trips only its own circuit instead of every circuit on a shared RCD.
Sources
- IEC 60898-1: Circuit-breakers for overcurrent protection for household and similar installations
- IEC 60947-2: Low-voltage switchgear: circuit-breakers
- IEC 61008-1 / IEC 61009-1: RCCBs and RCBOs; IEC 62606: arc fault detection devices
- UL 489, UL 943 (GFCI), UL 1699 (AFCI)
- NFPA 70 (NEC) 240.6(A) standard ampere ratings; 210.8 GFCI; 210.12 AFCI
- ABB System pro M compact S200 technical data (B, C, D, K, Z characteristics)
- DIN 43880: built-in equipment for electrical installations, overall dimensions (17.5 mm module)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.