Insulation R-Value per Inch and λ by Material

Thermal performance of common insulation materials in US units (R per inch) and metric (λ, W/m·K), plus standard batt thicknesses and code minimums. The key fact: R per inch × λ = 0.144, so λ 0.040 W/m·K is about R-3.6 per inch.

25 sizesChecked 2026-11-155 sources
R-0R-2R-4R-6R-8Fiberglass battMineral (rock) wool battLoose-fill fiberglassCelluloseOpen-cell spray foamClosed-cell spray foamExpanded polystyreneExtruded polystyrenePolyisocyanurateMineral wool boardPIR / PUR boardPhenolic foam boardGlass woolStone woolEPS incl. graphite EPSWood fibre boardExpanded cork boardSoftwood lumberR per inch (ft²·°F·h/Btu per in)
Typical R-value per inch ranges at 75 °F mean temperature. European products are shown from their declared λ.Proportions shown, not to scale

Size chartSort by any column, or filter to find a row

25 of 25
MaterialR per inch (ft²·°F·h/Btu)λ, W/(m·K)RSI per 100 mm (m²·K/W)R-value (US)tThicknessmminmm · inTypical use
Fibrous insulation (US typical values)
Fiberglass batt2.9–4.30.034–0.0502.01–2.98———
Mineral (rock) wool batt3.0–4.30.034–0.0482.08–2.98———
Loose-fill fiberglass2.2–2.90.050–0.0661.53–2.01———
Cellulose (blown)3.2–3.80.038–0.0452.22–2.63———
Mineral wool board4.0–4.30.034–0.0362.77–2.98———
Foam insulation (US typical values)
Open-cell spray foam3.5–3.80.038–0.0412.43–2.63———
Closed-cell spray foam5.5–7.00.021–0.0263.81–4.85———
Expanded polystyrene (EPS)3.6–4.20.034–0.0402.50–2.91———
Extruded polystyrene (XPS)5.00.0293.47———
Polyisocyanurate (foil-faced)5.6–6.50.022–0.0263.88–4.51———
European products (declared λD)
PIR / PUR board (EU)5.2–6.60.022–0.0283.57–4.55———
Phenolic foam board6.3–8.00.018–0.0234.35–5.55———
Glass wool (EU λD)3.3–4.50.032–0.0442.27–3.13———
Stone wool (EU λD)3.6–4.20.034–0.0402.50–2.94———
EPS incl. graphite EPS (EU λD)3.8–4.80.030–0.0382.63–3.33———
Wood fibre board2.9–3.80.038–0.0502.00–2.63———
Expanded cork board3.2–3.90.037–0.0452.22–2.70———
For comparison
Softwood lumber (for comparison)1.3–1.40.102–0.1150.87–0.98———
Fiberglass batts: R-value and thickness
R-11 batt———11893 1/22×4 wall cavity (3-1/2 in)
R-13 batt———13893 1/22×4 wall cavity (3-1/2 in)
R-15 batt———15893 1/22×4 wall cavity (3-1/2 in)
R-19 batt———191596.2522×6 wall cavity (5-1/2 in)
R-21 batt———211405 1/22×6 wall cavity (5-1/2 in)
R-30 batt———30241–2609.5–10.248Attic / ceiling
R-38 batt———38305–31812–12.5Attic / ceiling

R, RSI, U and λ

R-value is thermal resistance of a layer: US units ft²·°F·h/Btu, metric RSI in m²·K/W. R-1 = RSI 0.176. Layers in series add up: R-13 batt + R-5 foam = R-18.

λ (lambda, also k) is the conductivity of the material in W/(m·K). For a layer of thickness d in metres, RSI = d / λ. 100 mm at λ 0.035 = RSI 2.86 = R-16.2.

U-value is the reciprocal of the total resistance of the whole assembly including air films and framing, in W/(m²·K) or Btu/(h·ft²·°F). Codes in Europe regulate U-values; US codes give prescriptive R-values and U-factor alternatives.

Values in the chart are typical ranges at about 75 °F (24 °C) mean temperature. Use the R-value printed on the product (required by the FTC R-value rule in the US) or the declared λD on the CE label for calculations.

About Insulation R-Values

Batts only reach the labelled R-value at full thickness: an R-19 batt (6-1/4 in) squeezed into a 5-1/2-in 2×6 cavity performs at about R-18; a 2×6 wall should get R-20 or R-21 high-density batts made for that depth.

Studs are thermal bridges. Softwood is about R-1.25 to R-1.4 per inch, so a 2×4 stud (3-1/2 in) is roughly R-4.4 to R-4.9 against R-13 to R-15 in the cavity. Framing covers roughly a quarter of a typical wall, which is why codes push continuous insulation ("ci") outside the studs.

Polyisocyanurate loses part of its R-value at low temperatures (below about 50 °F mean); for cold-climate exterior insulation designers often use R-5 per inch for polyiso, not its 75 °F label. XPS slowly loses R-value over decades as blowing agent diffuses out.

Loose-fill settles: cellulose by up to about 20 %. Blow attics to the installed-thickness line on the manufacturer's coverage chart, not to the initial depth.

2021 IECC minimum insulation R-values (Table R402.1.3)

Prescriptive minimums for new homes, by climate zone. "ci" = continuous insulation; "13+5ci" = R-13 cavity plus R-5 continuous. Slab: R-value and depth. Local amendments are common, so check the edition your jurisdiction adopted (many states still use 2015 or 2018 values).

ZoneCeilingWood-frame wallFloorBasement wallSlabCrawl space wall
0–13013 or 0+10ci13000
24913 or 0+10ci13000
34920 or 13+5ci or 0+15ci195ci or 1310ci, 2 ft5ci or 13
4 (not marine)6030 or 20+5ci or 13+10ci or 0+20ci1910ci or 1310ci, 4 ft10ci or 13
5 and 4C6030 or 20+5ci or 13+10ci or 0+20ci3015ci or 19 or 13+5ci10ci, 4 ft15ci or 19 or 13+5ci
66030 or 20+5ci or 13+10ci or 0+20ci3015ci or 19 or 13+5ci10ci, 4 ft15ci or 19 or 13+5ci
7–86030 or 20+5ci or 13+10ci or 0+20ci3815ci or 19 or 13+5ci10ci, 4 ft15ci or 19 or 13+5ci

Converting R-value and λ

FromToMultiply by
R (US)RSI (m²·K/W)0.1761
RSIR (US)5.678
R per inchλ in W/(m·K)λ = 0.1442 ÷ R per inch
λ in W/(m·K)R per inchR/in = 0.1442 ÷ λ
U (W/m²K)U (Btu/h·ft²·°F)0.1761

Questions

What is the R-value per inch of fiberglass?

About R-2.9 to R-4.3 per inch for batts (standard batts R-3.1–3.4, high-density up to R-4.3) and R-2.2 to R-2.9 for blown loose-fill.

What is the R-value of spray foam per inch?

Open-cell about R-3.5 to R-3.8 per inch; closed-cell about R-5.5 to R-7 per inch (most products are labelled R-6 to R-7).

How thick is R-13 and R-19 insulation?

R-13 fiberglass batts are 3-1/2 in (for 2×4 walls); R-19 batts are 6-1/4 in. R-21 high-density batts fit a 5-1/2-in 2×6 cavity.

How do I convert λ to R-value per inch?

R per inch = 0.1442 ÷ λ. λ 0.035 W/(m·K) → R-4.1 per inch; λ 0.022 → R-6.6 per inch.

What attic insulation R-value is required?

Under the 2021 IECC: R-30 in zones 0–1, R-49 in zones 2–3 and R-60 in zones 4–8. Earlier editions (2018) required R-38 in zones 2–3 and R-49 in 4–8.

Sources

  1. US Department of Energy: Energy Saver: Insulation materials and R-values
  2. ASHRAE Handbook: Fundamentals, ch. 26 Heat, air and moisture control in building assemblies (material properties)
  3. ASTM C578 (polystyrene), C1289 (polyiso), C665 (mineral fiber batts): thermal resistance requirements
  4. 2021 IECC Table R402.1.3: Insulation minimum R-values by climate zone; PNNL Building America Solution Center summary
  5. EN 13162–13171: Thermal insulation products for buildings, factory-made products (declared λD)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.