Insulation R-Value per Inch and λ by Material
Thermal performance of common insulation materials in US units (R per inch) and metric (λ, W/m·K), plus standard batt thicknesses and code minimums. The key fact: R per inch × λ = 0.144, so λ 0.040 W/m·K is about R-3.6 per inch.
Size chartSort by any column, or filter to find a row
| Material | R per inch (ft²·°F·h/Btu) | λ, W/(m·K) | RSI per 100 mm (m²·K/W) | R-value (US) | tThicknessmminmm · in | Typical use |
|---|---|---|---|---|---|---|
| Fibrous insulation (US typical values) | ||||||
| Fiberglass batt | 2.9–4.3 | 0.034–0.050 | 2.01–2.98 | — | — | — |
| Mineral (rock) wool batt | 3.0–4.3 | 0.034–0.048 | 2.08–2.98 | — | — | — |
| Loose-fill fiberglass | 2.2–2.9 | 0.050–0.066 | 1.53–2.01 | — | — | — |
| Cellulose (blown) | 3.2–3.8 | 0.038–0.045 | 2.22–2.63 | — | — | — |
| Mineral wool board | 4.0–4.3 | 0.034–0.036 | 2.77–2.98 | — | — | — |
| Foam insulation (US typical values) | ||||||
| Open-cell spray foam | 3.5–3.8 | 0.038–0.041 | 2.43–2.63 | — | — | — |
| Closed-cell spray foam | 5.5–7.0 | 0.021–0.026 | 3.81–4.85 | — | — | — |
| Expanded polystyrene (EPS) | 3.6–4.2 | 0.034–0.040 | 2.50–2.91 | — | — | — |
| Extruded polystyrene (XPS) | 5.0 | 0.029 | 3.47 | — | — | — |
| Polyisocyanurate (foil-faced) | 5.6–6.5 | 0.022–0.026 | 3.88–4.51 | — | — | — |
| European products (declared λD) | ||||||
| PIR / PUR board (EU) | 5.2–6.6 | 0.022–0.028 | 3.57–4.55 | — | — | — |
| Phenolic foam board | 6.3–8.0 | 0.018–0.023 | 4.35–5.55 | — | — | — |
| Glass wool (EU λD) | 3.3–4.5 | 0.032–0.044 | 2.27–3.13 | — | — | — |
| Stone wool (EU λD) | 3.6–4.2 | 0.034–0.040 | 2.50–2.94 | — | — | — |
| EPS incl. graphite EPS (EU λD) | 3.8–4.8 | 0.030–0.038 | 2.63–3.33 | — | — | — |
| Wood fibre board | 2.9–3.8 | 0.038–0.050 | 2.00–2.63 | — | — | — |
| Expanded cork board | 3.2–3.9 | 0.037–0.045 | 2.22–2.70 | — | — | — |
| For comparison | ||||||
| Softwood lumber (for comparison) | 1.3–1.4 | 0.102–0.115 | 0.87–0.98 | — | — | — |
| Fiberglass batts: R-value and thickness | ||||||
| R-11 batt | — | — | — | 11 | 893 1/2 | 2×4 wall cavity (3-1/2 in) |
| R-13 batt | — | — | — | 13 | 893 1/2 | 2×4 wall cavity (3-1/2 in) |
| R-15 batt | — | — | — | 15 | 893 1/2 | 2×4 wall cavity (3-1/2 in) |
| R-19 batt | — | — | — | 19 | 1596.252 | 2×6 wall cavity (5-1/2 in) |
| R-21 batt | — | — | — | 21 | 1405 1/2 | 2×6 wall cavity (5-1/2 in) |
| R-30 batt | — | — | — | 30 | 241–2609.5–10.248 | Attic / ceiling |
| R-38 batt | — | — | — | 38 | 305–31812–12.5 | Attic / ceiling |
No exact match. The nearest sizes:
R, RSI, U and λ
R-value is thermal resistance of a layer: US units ft²·°F·h/Btu, metric RSI in m²·K/W. R-1 = RSI 0.176. Layers in series add up: R-13 batt + R-5 foam = R-18.
λ (lambda, also k) is the conductivity of the material in W/(m·K). For a layer of thickness d in metres, RSI = d / λ. 100 mm at λ 0.035 = RSI 2.86 = R-16.2.
U-value is the reciprocal of the total resistance of the whole assembly including air films and framing, in W/(m²·K) or Btu/(h·ft²·°F). Codes in Europe regulate U-values; US codes give prescriptive R-values and U-factor alternatives.
Values in the chart are typical ranges at about 75 °F (24 °C) mean temperature. Use the R-value printed on the product (required by the FTC R-value rule in the US) or the declared λD on the CE label for calculations.
About Insulation R-Values
Batts only reach the labelled R-value at full thickness: an R-19 batt (6-1/4 in) squeezed into a 5-1/2-in 2×6 cavity performs at about R-18; a 2×6 wall should get R-20 or R-21 high-density batts made for that depth.
Studs are thermal bridges. Softwood is about R-1.25 to R-1.4 per inch, so a 2×4 stud (3-1/2 in) is roughly R-4.4 to R-4.9 against R-13 to R-15 in the cavity. Framing covers roughly a quarter of a typical wall, which is why codes push continuous insulation ("ci") outside the studs.
Polyisocyanurate loses part of its R-value at low temperatures (below about 50 °F mean); for cold-climate exterior insulation designers often use R-5 per inch for polyiso, not its 75 °F label. XPS slowly loses R-value over decades as blowing agent diffuses out.
Loose-fill settles: cellulose by up to about 20 %. Blow attics to the installed-thickness line on the manufacturer's coverage chart, not to the initial depth.
2021 IECC minimum insulation R-values (Table R402.1.3)
Prescriptive minimums for new homes, by climate zone. "ci" = continuous insulation; "13+5ci" = R-13 cavity plus R-5 continuous. Slab: R-value and depth. Local amendments are common, so check the edition your jurisdiction adopted (many states still use 2015 or 2018 values).
| Zone | Ceiling | Wood-frame wall | Floor | Basement wall | Slab | Crawl space wall |
|---|---|---|---|---|---|---|
| 0–1 | 30 | 13 or 0+10ci | 13 | 0 | 0 | 0 |
| 2 | 49 | 13 or 0+10ci | 13 | 0 | 0 | 0 |
| 3 | 49 | 20 or 13+5ci or 0+15ci | 19 | 5ci or 13 | 10ci, 2 ft | 5ci or 13 |
| 4 (not marine) | 60 | 30 or 20+5ci or 13+10ci or 0+20ci | 19 | 10ci or 13 | 10ci, 4 ft | 10ci or 13 |
| 5 and 4C | 60 | 30 or 20+5ci or 13+10ci or 0+20ci | 30 | 15ci or 19 or 13+5ci | 10ci, 4 ft | 15ci or 19 or 13+5ci |
| 6 | 60 | 30 or 20+5ci or 13+10ci or 0+20ci | 30 | 15ci or 19 or 13+5ci | 10ci, 4 ft | 15ci or 19 or 13+5ci |
| 7–8 | 60 | 30 or 20+5ci or 13+10ci or 0+20ci | 38 | 15ci or 19 or 13+5ci | 10ci, 4 ft | 15ci or 19 or 13+5ci |
Converting R-value and λ
| From | To | Multiply by |
|---|---|---|
| R (US) | RSI (m²·K/W) | 0.1761 |
| RSI | R (US) | 5.678 |
| R per inch | λ in W/(m·K) | λ = 0.1442 ÷ R per inch |
| λ in W/(m·K) | R per inch | R/in = 0.1442 ÷ λ |
| U (W/m²K) | U (Btu/h·ft²·°F) | 0.1761 |
Questions
What is the R-value per inch of fiberglass?
About R-2.9 to R-4.3 per inch for batts (standard batts R-3.1–3.4, high-density up to R-4.3) and R-2.2 to R-2.9 for blown loose-fill.
What is the R-value of spray foam per inch?
Open-cell about R-3.5 to R-3.8 per inch; closed-cell about R-5.5 to R-7 per inch (most products are labelled R-6 to R-7).
How thick is R-13 and R-19 insulation?
R-13 fiberglass batts are 3-1/2 in (for 2×4 walls); R-19 batts are 6-1/4 in. R-21 high-density batts fit a 5-1/2-in 2×6 cavity.
How do I convert λ to R-value per inch?
R per inch = 0.1442 ÷ λ. λ 0.035 W/(m·K) → R-4.1 per inch; λ 0.022 → R-6.6 per inch.
What attic insulation R-value is required?
Under the 2021 IECC: R-30 in zones 0–1, R-49 in zones 2–3 and R-60 in zones 4–8. Earlier editions (2018) required R-38 in zones 2–3 and R-49 in 4–8.
Sources
- US Department of Energy: Energy Saver: Insulation materials and R-values
- ASHRAE Handbook: Fundamentals, ch. 26 Heat, air and moisture control in building assemblies (material properties)
- ASTM C578 (polystyrene), C1289 (polyiso), C665 (mineral fiber batts): thermal resistance requirements
- 2021 IECC Table R402.1.3: Insulation minimum R-values by climate zone; PNNL Building America Solution Center summary
- EN 13162–13171: Thermal insulation products for buildings, factory-made products (declared λD)