Cable Current-Carrying Capacity (IEC 60364-5-52)

Current-carrying capacities of copper cables from IEC 60364-5-52 Annex B, the table behind most metric cable sizing (HD 60364, VDE 0298-4 style, AS/NZS and national codes derived from it). Example: 2.5 mm² PVC cable clipped to a wall (method C) carries 27 A with two loaded conductors and 24 A with three, at 30 °C ambient.

64 rowsChecked 2026-11-154 sources
A1cores, insulated wallA2cable, insulated wallB1cores in conduitB2cable in conduitCclipped directD1duct in ground
Shaded: thermal insulation (A1, A2); hatched: wall or soil.Schematic, not to scale

Size chartCopper, amperes, 30 °C air / 20 °C ground

64 of 64 rows
SizeMethod A1AMethod A2AMethod B1AMethod B2AMethod CAMethod D1A
PVC 70 °C, 2 loaded conductors (B.52.2)
1.5 mm²14.51417.516.519.522
2.5 mm²19.518.524232729
4 mm²262532303637
6 mm²343241384646
10 mm²464357526360
16 mm²615776698578
25 mm²80751019011299
35 mm²9992125111138119
50 mm²119110151133168140
70 mm²151139192168213173
95 mm²182167232201258204
120 mm²210192269232299231
150 mm²240219300258344261
185 mm²273248341294392292
240 mm²321291400344461336
300 mm²367334458394530379
PVC 70 °C, 3 loaded conductors (B.52.4)
1.5 mm²13.51315.51517.518
2.5 mm²1817.521202424
4 mm²242328273230
6 mm²312936344138
10 mm²423950465750
16 mm²565268627664
25 mm²736889809682
35 mm²89831109911998
50 mm²10899134118144116
70 mm²136125171149184143
95 mm²164150207179223169
120 mm²188172239206259192
150 mm²216196262225299217
185 mm²245223296255341243
240 mm²286261346297403280
300 mm²328298394339464316
XLPE/EPR 90 °C, 2 loaded conductors (B.52.3)
1.5 mm²1918.523222425
2.5 mm²262531303333
4 mm²353342404543
6 mm²454254515853
10 mm²615775698071
16 mm²81761009110791
25 mm²10699133119138116
35 mm²131121164146171139
50 mm²158145198175209164
70 mm²200183253221269203
95 mm²241220306265328239
120 mm²278253354305382271
150 mm²318290393334441306
185 mm²362329449384506343
240 mm²424386528459599395
300 mm²486442603532693446
XLPE/EPR 90 °C, 3 loaded conductors (B.52.5)
1.5 mm²1716.52019.52221
2.5 mm²232228263028
4 mm²313037354036
6 mm²403848445244
10 mm²545166607158
16 mm²736888809675
25 mm²958911710511996
35 mm²117109144128147115
50 mm²141130175154179135
70 mm²179164222194229167
95 mm²216197269233278197
120 mm²249227312268322223
150 mm²285259342300371251
185 mm²324295384340424281
240 mm²380346450398500324
300 mm²435396514455576365

How to read the table

Pick the insulation first: PVC (thermoplastic, conductor limit 70 °C: H07V-K, H05VV-F, NYM, twin-and-earth) or XLPE/EPR (thermoset, 90 °C: N2XH, NYY with XLPE, SWA cable, CU/XLPE/PVC). Then count the loaded conductors: a single-phase circuit has two (line and neutral), a balanced three-phase circuit three. The protective conductor never counts.

Next find the reference installation method that matches how the cable is run. A1 and A2 are in conduit inside a thermally insulated wall (the worst case), B1 and B2 in conduit or trunking on a wall, C clipped directly to a wall or ceiling, D1 in a duct in the ground. "Cores" (A1, B1) means single insulated conductors such as H07V-K pulled into conduit; "cable" (A2, B2) means a sheathed multicore cable inside the conduit.

The values are for 30 °C air (20 °C ground for D1), one circuit on its own. Real installations almost always need correction factors: multiply the table value by the ambient-temperature factor and the grouping factor (tables below). The result Iz must be at least the design current, and the protective device rating In must lie between them (Ib ≤ In ≤ Iz).

About Cable Ampacity (IEC)

These are the copper columns of IEC 60364-5-52:2009 Tables B.52.2 to B.52.5 for methods A1, A2, B1, B2, C and D1. Aluminium conductors, method D2 (cable direct in ground) and the free-air methods E, F and G (Tables B.52.10 to B.52.13) are not reproduced here. National versions such as BS 7671 Appendix 4 use the same physics but their own method letters and slightly different values. Use the table your local code references.

XLPE carries 20–30 % more current than PVC of the same size because its conductor limit is 90 °C instead of 70 °C. That headroom is only usable if the terminals and equipment accept a 90 °C conductor; many devices are rated for 70 °C conductors, in which case the PVC column is the safe one.

Method D1 values in the 2009 edition assume a soil thermal resistivity of 2.5 K·m/W, a conservative value for dry soil. The 2001 edition used a lower soil resistivity and gave higher ground ratings, so do not mix D values from different editions.

Ambient temperature correction (Table B.52.14, cables in air)

Multiply the table value by the factor for the actual air temperature around the cable. Reference 30 °C = 1.00.

Ambient °C101520253540455055607080
PVC1.221.171.121.060.940.870.790.710.610.50——
XLPE / EPR1.151.121.081.040.960.910.870.820.760.710.580.41

Grouping correction (Table B.52.17, bunched, on a surface, embedded or enclosed)

Number of circuits or multicore cables run together (methods A to F). Single layers on walls, trays and ladders have their own, milder rows in the standard.

Circuits123456789121620
Factor1.000.800.700.650.600.570.540.520.500.450.410.38

Worked example

A 3-phase 20 A motor circuit in PVC cable (3 loaded conductors), run in conduit on a wall (B2) with two other circuits, at 35 °C. Factors: 0.94 × 0.70 = 0.658. Required tabulated capacity: 20 / 0.658 = 30.4 A. In the PVC · 3 group, 4 mm² gives 27 A (too small) and 6 mm² gives 34 A → 34 × 0.658 = 22.4 A ≥ 20 A. Then check voltage drop and short-circuit withstand, which can push the size up further.

Questions

How many amps can 2.5 mm² cable carry?

Copper PVC 2.5 mm² with two loaded conductors: 19.5 A in conduit in an insulated wall (A1), 24 A in conduit on a wall (B1), 27 A clipped direct (C), at 30 °C. With three loaded conductors it is 18, 21 and 24 A. XLPE 2.5 mm² gives 26, 31 and 33 A (two loaded).

How many amps can 1.5 mm² cable carry?

Copper PVC 1.5 mm², two loaded conductors: 14.5 A (A1), 17.5 A (B1), 19.5 A (C). That is why 1.5 mm² lighting circuits are normally protected at 10 A or 16 A depending on the installation method and national rules.

What does "loaded conductors" mean?

The conductors that carry the load current: 2 for single-phase (L and N), 3 for balanced three-phase (L1, L2, L3). The neutral of a balanced three-phase circuit and the protective earth conductor are not counted. With heavy third-harmonic currents the neutral does count and an extra factor applies.

Which installation method is a cable in a plastered wall?

A cable embedded directly in masonry or plaster is treated like method C (clipped direct) in the IEC 60364-5-52 list of installation methods. If the wall contains thermal insulation around the cable or conduit, use A1/A2, which are 25–30 % lower.

What size cable for 32 A?

With PVC, two loaded conductors and no derating: 6 mm² in methods A1/A2 (34/32 A), 4 mm² in B1 (32 A) or C (36 A). With three circuits bunched (0.70) a C-run needs 32 / 0.70 = 45.7 A → 6 mm² (46 A × 0.70 = 32.2 A) just passes; 10 mm² leaves margin for voltage drop.

Sources

  1. IEC 60364-5-52:2009+AMD1:2011, Low-voltage electrical installations, Part 5-52: Wiring systems, Annex B (Tables B.52.2–B.52.5, B.52.14, B.52.17)
  2. HD 60364-5-52 / PN-HD 60364-5-52:2011, European harmonised adoption of the same tables
  3. TiSoft: IEC 60364-5-52 current-carrying capacity tables B.52.2 to B.52.5 (reproduction)
  4. Kalkulatorpro: conductor current-carrying capacity per PN-HD 60364-5-52

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.