Cable Current-Carrying Capacity (IEC 60364-5-52)
Current-carrying capacities of copper cables from IEC 60364-5-52 Annex B, the table behind most metric cable sizing (HD 60364, VDE 0298-4 style, AS/NZS and national codes derived from it). Example: 2.5 mm² PVC cable clipped to a wall (method C) carries 27 A with two loaded conductors and 24 A with three, at 30 °C ambient.
Size chartCopper, amperes, 30 °C air / 20 °C ground
| Size | Method A1A | Method A2A | Method B1A | Method B2A | Method CA | Method D1A |
|---|---|---|---|---|---|---|
| PVC 70 °C, 2 loaded conductors (B.52.2) | ||||||
| 1.5 mm² | 14.5 | 14 | 17.5 | 16.5 | 19.5 | 22 |
| 2.5 mm² | 19.5 | 18.5 | 24 | 23 | 27 | 29 |
| 4 mm² | 26 | 25 | 32 | 30 | 36 | 37 |
| 6 mm² | 34 | 32 | 41 | 38 | 46 | 46 |
| 10 mm² | 46 | 43 | 57 | 52 | 63 | 60 |
| 16 mm² | 61 | 57 | 76 | 69 | 85 | 78 |
| 25 mm² | 80 | 75 | 101 | 90 | 112 | 99 |
| 35 mm² | 99 | 92 | 125 | 111 | 138 | 119 |
| 50 mm² | 119 | 110 | 151 | 133 | 168 | 140 |
| 70 mm² | 151 | 139 | 192 | 168 | 213 | 173 |
| 95 mm² | 182 | 167 | 232 | 201 | 258 | 204 |
| 120 mm² | 210 | 192 | 269 | 232 | 299 | 231 |
| 150 mm² | 240 | 219 | 300 | 258 | 344 | 261 |
| 185 mm² | 273 | 248 | 341 | 294 | 392 | 292 |
| 240 mm² | 321 | 291 | 400 | 344 | 461 | 336 |
| 300 mm² | 367 | 334 | 458 | 394 | 530 | 379 |
| PVC 70 °C, 3 loaded conductors (B.52.4) | ||||||
| 1.5 mm² | 13.5 | 13 | 15.5 | 15 | 17.5 | 18 |
| 2.5 mm² | 18 | 17.5 | 21 | 20 | 24 | 24 |
| 4 mm² | 24 | 23 | 28 | 27 | 32 | 30 |
| 6 mm² | 31 | 29 | 36 | 34 | 41 | 38 |
| 10 mm² | 42 | 39 | 50 | 46 | 57 | 50 |
| 16 mm² | 56 | 52 | 68 | 62 | 76 | 64 |
| 25 mm² | 73 | 68 | 89 | 80 | 96 | 82 |
| 35 mm² | 89 | 83 | 110 | 99 | 119 | 98 |
| 50 mm² | 108 | 99 | 134 | 118 | 144 | 116 |
| 70 mm² | 136 | 125 | 171 | 149 | 184 | 143 |
| 95 mm² | 164 | 150 | 207 | 179 | 223 | 169 |
| 120 mm² | 188 | 172 | 239 | 206 | 259 | 192 |
| 150 mm² | 216 | 196 | 262 | 225 | 299 | 217 |
| 185 mm² | 245 | 223 | 296 | 255 | 341 | 243 |
| 240 mm² | 286 | 261 | 346 | 297 | 403 | 280 |
| 300 mm² | 328 | 298 | 394 | 339 | 464 | 316 |
| XLPE/EPR 90 °C, 2 loaded conductors (B.52.3) | ||||||
| 1.5 mm² | 19 | 18.5 | 23 | 22 | 24 | 25 |
| 2.5 mm² | 26 | 25 | 31 | 30 | 33 | 33 |
| 4 mm² | 35 | 33 | 42 | 40 | 45 | 43 |
| 6 mm² | 45 | 42 | 54 | 51 | 58 | 53 |
| 10 mm² | 61 | 57 | 75 | 69 | 80 | 71 |
| 16 mm² | 81 | 76 | 100 | 91 | 107 | 91 |
| 25 mm² | 106 | 99 | 133 | 119 | 138 | 116 |
| 35 mm² | 131 | 121 | 164 | 146 | 171 | 139 |
| 50 mm² | 158 | 145 | 198 | 175 | 209 | 164 |
| 70 mm² | 200 | 183 | 253 | 221 | 269 | 203 |
| 95 mm² | 241 | 220 | 306 | 265 | 328 | 239 |
| 120 mm² | 278 | 253 | 354 | 305 | 382 | 271 |
| 150 mm² | 318 | 290 | 393 | 334 | 441 | 306 |
| 185 mm² | 362 | 329 | 449 | 384 | 506 | 343 |
| 240 mm² | 424 | 386 | 528 | 459 | 599 | 395 |
| 300 mm² | 486 | 442 | 603 | 532 | 693 | 446 |
| XLPE/EPR 90 °C, 3 loaded conductors (B.52.5) | ||||||
| 1.5 mm² | 17 | 16.5 | 20 | 19.5 | 22 | 21 |
| 2.5 mm² | 23 | 22 | 28 | 26 | 30 | 28 |
| 4 mm² | 31 | 30 | 37 | 35 | 40 | 36 |
| 6 mm² | 40 | 38 | 48 | 44 | 52 | 44 |
| 10 mm² | 54 | 51 | 66 | 60 | 71 | 58 |
| 16 mm² | 73 | 68 | 88 | 80 | 96 | 75 |
| 25 mm² | 95 | 89 | 117 | 105 | 119 | 96 |
| 35 mm² | 117 | 109 | 144 | 128 | 147 | 115 |
| 50 mm² | 141 | 130 | 175 | 154 | 179 | 135 |
| 70 mm² | 179 | 164 | 222 | 194 | 229 | 167 |
| 95 mm² | 216 | 197 | 269 | 233 | 278 | 197 |
| 120 mm² | 249 | 227 | 312 | 268 | 322 | 223 |
| 150 mm² | 285 | 259 | 342 | 300 | 371 | 251 |
| 185 mm² | 324 | 295 | 384 | 340 | 424 | 281 |
| 240 mm² | 380 | 346 | 450 | 398 | 500 | 324 |
| 300 mm² | 435 | 396 | 514 | 455 | 576 | 365 |
No exact match. The nearest sizes:
How to read the table
Pick the insulation first: PVC (thermoplastic, conductor limit 70 °C: H07V-K, H05VV-F, NYM, twin-and-earth) or XLPE/EPR (thermoset, 90 °C: N2XH, NYY with XLPE, SWA cable, CU/XLPE/PVC). Then count the loaded conductors: a single-phase circuit has two (line and neutral), a balanced three-phase circuit three. The protective conductor never counts.
Next find the reference installation method that matches how the cable is run. A1 and A2 are in conduit inside a thermally insulated wall (the worst case), B1 and B2 in conduit or trunking on a wall, C clipped directly to a wall or ceiling, D1 in a duct in the ground. "Cores" (A1, B1) means single insulated conductors such as H07V-K pulled into conduit; "cable" (A2, B2) means a sheathed multicore cable inside the conduit.
The values are for 30 °C air (20 °C ground for D1), one circuit on its own. Real installations almost always need correction factors: multiply the table value by the ambient-temperature factor and the grouping factor (tables below). The result Iz must be at least the design current, and the protective device rating In must lie between them (Ib ≤ In ≤ Iz).
About Cable Ampacity (IEC)
These are the copper columns of IEC 60364-5-52:2009 Tables B.52.2 to B.52.5 for methods A1, A2, B1, B2, C and D1. Aluminium conductors, method D2 (cable direct in ground) and the free-air methods E, F and G (Tables B.52.10 to B.52.13) are not reproduced here. National versions such as BS 7671 Appendix 4 use the same physics but their own method letters and slightly different values. Use the table your local code references.
XLPE carries 20–30 % more current than PVC of the same size because its conductor limit is 90 °C instead of 70 °C. That headroom is only usable if the terminals and equipment accept a 90 °C conductor; many devices are rated for 70 °C conductors, in which case the PVC column is the safe one.
Method D1 values in the 2009 edition assume a soil thermal resistivity of 2.5 K·m/W, a conservative value for dry soil. The 2001 edition used a lower soil resistivity and gave higher ground ratings, so do not mix D values from different editions.
Ambient temperature correction (Table B.52.14, cables in air)
Multiply the table value by the factor for the actual air temperature around the cable. Reference 30 °C = 1.00.
| Ambient °C | 10 | 15 | 20 | 25 | 35 | 40 | 45 | 50 | 55 | 60 | 70 | 80 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| PVC | 1.22 | 1.17 | 1.12 | 1.06 | 0.94 | 0.87 | 0.79 | 0.71 | 0.61 | 0.50 | — | — |
| XLPE / EPR | 1.15 | 1.12 | 1.08 | 1.04 | 0.96 | 0.91 | 0.87 | 0.82 | 0.76 | 0.71 | 0.58 | 0.41 |
Grouping correction (Table B.52.17, bunched, on a surface, embedded or enclosed)
Number of circuits or multicore cables run together (methods A to F). Single layers on walls, trays and ladders have their own, milder rows in the standard.
| Circuits | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 12 | 16 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Factor | 1.00 | 0.80 | 0.70 | 0.65 | 0.60 | 0.57 | 0.54 | 0.52 | 0.50 | 0.45 | 0.41 | 0.38 |
Worked example
A 3-phase 20 A motor circuit in PVC cable (3 loaded conductors), run in conduit on a wall (B2) with two other circuits, at 35 °C. Factors: 0.94 × 0.70 = 0.658. Required tabulated capacity: 20 / 0.658 = 30.4 A. In the PVC · 3 group, 4 mm² gives 27 A (too small) and 6 mm² gives 34 A → 34 × 0.658 = 22.4 A ≥ 20 A. Then check voltage drop and short-circuit withstand, which can push the size up further.
Questions
How many amps can 2.5 mm² cable carry?
Copper PVC 2.5 mm² with two loaded conductors: 19.5 A in conduit in an insulated wall (A1), 24 A in conduit on a wall (B1), 27 A clipped direct (C), at 30 °C. With three loaded conductors it is 18, 21 and 24 A. XLPE 2.5 mm² gives 26, 31 and 33 A (two loaded).
How many amps can 1.5 mm² cable carry?
Copper PVC 1.5 mm², two loaded conductors: 14.5 A (A1), 17.5 A (B1), 19.5 A (C). That is why 1.5 mm² lighting circuits are normally protected at 10 A or 16 A depending on the installation method and national rules.
What does "loaded conductors" mean?
The conductors that carry the load current: 2 for single-phase (L and N), 3 for balanced three-phase (L1, L2, L3). The neutral of a balanced three-phase circuit and the protective earth conductor are not counted. With heavy third-harmonic currents the neutral does count and an extra factor applies.
Which installation method is a cable in a plastered wall?
A cable embedded directly in masonry or plaster is treated like method C (clipped direct) in the IEC 60364-5-52 list of installation methods. If the wall contains thermal insulation around the cable or conduit, use A1/A2, which are 25–30 % lower.
What size cable for 32 A?
With PVC, two loaded conductors and no derating: 6 mm² in methods A1/A2 (34/32 A), 4 mm² in B1 (32 A) or C (36 A). With three circuits bunched (0.70) a C-run needs 32 / 0.70 = 45.7 A → 6 mm² (46 A × 0.70 = 32.2 A) just passes; 10 mm² leaves margin for voltage drop.
Sources
- IEC 60364-5-52:2009+AMD1:2011, Low-voltage electrical installations, Part 5-52: Wiring systems, Annex B (Tables B.52.2–B.52.5, B.52.14, B.52.17)
- HD 60364-5-52 / PN-HD 60364-5-52:2011, European harmonised adoption of the same tables
- TiSoft: IEC 60364-5-52 current-carrying capacity tables B.52.2 to B.52.5 (reproduction)
- Kalkulatorpro: conductor current-carrying capacity per PN-HD 60364-5-52
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.