Electrical Wire Color Codes by Country
Phase (line), neutral and protective-earth conductor colors in the main wiring standards. The one rule that holds almost everywhere: green-yellow (or green) is earth only. Never use it for anything else. Everything else differs: blue is neutral in Europe but a phase in the US and Canada; black is a phase in Europe and the US but the old UK neutral.
Color tableFixed AC wiring; DC colors below the table
| Standard / system | L1 / line | L2 | L3 | Neutral | Protective earth |
|---|---|---|---|---|---|
| IEC 60445 / EU, UK (3-phase) | brown | black | grey | blue | green-yellow |
| IEC 60445 / EU, UK (1-phase) | brown | — | — | blue | green-yellow |
| UK before 2004 | red | yellow | blue | black | green-yellow |
| US 208Y/120 V | black | red | blue | white or grey | green (or green-yellow, or bare) |
| US 480Y/277 V | brown | orange | yellow | grey (or white) | green (or green-yellow, or bare) |
| US 120/240 V split-phase | black | red | — | white or grey | green (or green-yellow, or bare) |
| Canada (CEC) | red | black | blue | white or grey | green (or green-yellow, or bare) |
| Australia / NZ | red | white | blue | black | green-yellow |
| South Korea (KEC 2021) | brown | black | grey | blue | green-yellow |
| China (GB) | yellow | green | red | light blue | green-yellow |
| Japan 1-phase 3-wire | black | red | — | white or grey | green (or green-yellow, or bare) |
| Japan 3-phase 3-wire | red | white | black or blue | — | green (or green-yellow, or bare) |
| India (traditional) | red | yellow | blue | black | green (or green-yellow, or bare) |
No exact match. The nearest sizes:
How to use the table
Each row is one wiring system. L1, L2, L3 are the phase (line, "hot", "active") conductors; a single-phase circuit uses only L1 (or L1 and L2 in North American 120/240 V split-phase). N is the neutral ("grounded conductor" in the NEC). PE is the protective earth ("equipment grounding conductor").
Colors identify the conductor, they do not prove what it is. Old installations, re-used cores and DIY work break every rule, so always test before touching. In multicore cable, sleeving or tape (e.g. brown or L1/L2/L3 markers on black cores) is a permitted way to re-identify a conductor everywhere except for green-yellow.
About Wire Color Codes
Europe and the UK follow IEC 60445 through CENELEC HD 308: brown, black, grey for the three phases, blue for neutral, green-yellow for earth. Single-phase circuits and appliance cords use brown and blue. The UK switched with BS 7671 Amendment 2 (2004; mandatory for new work from April 2006), so British installations may contain both schemes. A warning label is required where old red/black meets new brown/blue. Old red is now brown, old black neutral is now blue, and old black (neutral) and new black (L2) are not the same thing.
The US NEC only fixes two things: the grounded (neutral) conductor is white or gray (200.6), and the equipment grounding conductor is green, green with yellow stripes, or bare (250.119). The phase colors are trade custom: black, red, blue on 120/208 V and 120/240 V systems, brown, orange, yellow on 277/480 V systems with a gray neutral so the two voltage systems cannot be confused in the same building. On a 120/240 V delta with a high leg, NEC 110.15 requires the high leg (208 V to neutral) to be marked orange.
Canada (CEC Rule 4-038) requires red, black, blue for three-phase AC phases, with white neutral and green bonding conductor. Australia and New Zealand (AS/NZS 3000) recommend red for single-phase active and still widely use red, white and blue for three phases with a black neutral, although light blue neutral and brown/black/grey actives are also accepted in harmonised cable.
South Korea adopted the IEC colors in the 2021 KEC (L1 brown, L2 black, L3 grey, N blue, PE green-yellow); older Korean installations used locally customary colors with a green earth. China uses yellow, green, red for L1, L2, L3 with light-blue neutral. Japan fixes only white for the grounded (neutral) conductor and green for earth; single-phase three-wire 100/200 V uses black and red for the two lines, and three-phase 200 V circuits are commonly red, white, black (or blue), where white marks the grounded phase. Japanese and Korean practice should be checked against site drawings.
Control and machine wiring inside panels follows different rules (IEC 60204-1, NFPA 79): typically black for AC power, red for AC control, dark blue for DC control and orange for circuits that stay live with the main switch off.
DC conductor colors
DC wiring has fewer settled conventions. The table shows the rules most often cited; automotive and solar PV practice (red positive, black negative) is custom, not code, in most places.
| System | Positive (L+) | Negative (L−) | Mid-wire / earthed (M) | Earth |
|---|---|---|---|---|
| UK BS 7671, two-wire unearthed | brown | grey | — | green-yellow |
| UK BS 7671, negative earthed | brown | blue (M) | — | green-yellow |
| UK BS 7671, three-wire | brown | grey | blue | green-yellow |
| US NEC 210.5(C)(2), branch circuits | red (or "+" marking) | black (or "−" marking) | — | green or bare |
| Vehicles, boats, PV (custom) | red | black | — | green / green-yellow |
Old and new UK colors
Single-phase: red → brown (line), black → blue (neutral). Three-phase: red → brown (L1), yellow → black (L2), blue → grey (L3), black → blue (N). Earth stays green-yellow (green before 1977).
Questions
What color is the neutral wire?
Blue in Europe, the UK (since 2004), Korea (since 2021) and other IEC countries; white or gray in the US and Canada; black in old UK wiring and in Australia (light blue also accepted); light blue in China; white in Japan.
What are the three-phase colors in Europe?
L1 brown, L2 black, L3 grey, with blue neutral and green-yellow earth (IEC 60445, HD 308 S2). The UK used red, yellow, blue with black neutral until 2004.
What are the US 480 V wire colors?
By custom brown, orange, yellow for L1, L2, L3 with a gray neutral on 277/480 V systems, and black, red, blue with white neutral on 120/208 V systems. The NEC itself only mandates white/gray for neutral and green/bare for ground.
Can I use a black wire as neutral?
In the US, a conductor 4 AWG or larger may be re-identified as neutral with white or gray marking at each termination; smaller conductors must have white or gray insulation (NEC 200.6). In IEC countries, blue is reserved for neutral where a neutral exists, and other cores may be marked with sleeves. Green-yellow can never be re-identified.
Is green-yellow always earth?
Yes. In every IEC country green-yellow is exclusively the protective conductor (PE or PEN with blue markings at the ends). In North America the equivalent is green or green with yellow stripes, or bare copper.
Sources
- IEC 60445:2021, Basic and safety principles for man-machine interface, marking and identification: identification of equipment terminals, conductor terminations and conductors
- CENELEC HD 308 S2: Identification of cores in cables and flexible cords
- IET: Harmonised cable colours and alphanumeric marking (BS 7671 Amendment 2:2004)
- NFPA 70 National Electrical Code: 200.6, 210.5, 250.119, 110.15
- CSA C22.1 Canadian Electrical Code: Rule 4-038
- Korea Electro-technical Code (KEC) 121.2: conductor identification (summary)
- AS/NZS 3000 Wiring Rules: clause 3.8, identification of conductors
- Panasonic: 単相3線式・中性線の色 (Japanese wiring practice)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.