IEC / European Cable Types (HAR Code) and Asian Equivalents
European cable names are a code, not a brand. H07RN-F 3G2.5 reads: harmonised (H), 450/750 V (07), rubber insulation (R), polychloroprene sheath (N), flexible conductor (-F), 3 cores including green-yellow (3G), 2.5 mm² each. The same logic decodes every H05… and H07… type below.
Cable typesTap a type for its cross-section and full specs
| Type | Voltage U0/U | Conductor | Insulation | Sheath | Max. conductor temp.°C°F | Cross-sections | Standard |
|---|---|---|---|---|---|---|---|
| Harmonised flexible cords | |||||||
| H03VV-F | 300/300 V | class 5 flexible | PVC | PVC | 70158 | — | EN 50525-2-11 |
| H05VV-F | 300/500 V | class 5 flexible | PVC | PVC | 70158 | — | EN 50525-2-11 |
| H05RR-F | 300/500 V | class 5 flexible | rubber (EI4) | rubber | 60140 | — | EN 50525-2-21 |
| H05RN-F | 300/500 V | class 5 flexible | rubber (EI4) | polychloroprene (CR) | 60140 | — | EN 50525-2-21 |
| H07RN-F | 450/750 V | class 5 flexible | rubber (EI4) | polychloroprene (CR) | 60140 | — | EN 50525-2-21 |
| Harmonised single-core wires | |||||||
| H05V-U | 300/500 V | class 1 solid | PVC | — | 70158 | — | EN 50525-2-31 |
| H05V-K | 300/500 V | class 5 flexible | PVC | — | 70158 | — | EN 50525-2-31 |
| H07V-U | 450/750 V | class 1 solid | PVC | — | 70158 | — | EN 50525-2-31 |
| H07V-R | 450/750 V | class 2 stranded | PVC | — | 70158 | — | EN 50525-2-31 |
| H07V-K | 450/750 V | class 5 flexible | PVC | — | 70158 | — | EN 50525-2-31 |
| H07Z1-K | 450/750 V | class 5 flexible | halogen-free (LSZH) | — | 70158 | — | EN 50525-3-31 |
| European national types | |||||||
| NYM-J | 300/500 V | class 1 solid | PVC | PVC | 70158 | — | DIN VDE 0250-204 |
| NYY-J | 0.6/1 kV | class 1 solid | PVC | PVC | 70158 | — | DIN VDE 0276-603 |
| N2XH-J | 0.6/1 kV | class 1 solid | XLPE | halogen-free | 90194 | — | DIN VDE 0276-604 |
| 6242Y (Twin & Earth) | 300/500 V | class 1 solid | PVC | PVC | 70158 | 1–16 mm² | BS 6004 |
| SWA (XLPE/SWA/PVC) | 600/1000 V | class 2 stranded | XLPE | PVC over steel wire armour | 90194 | — | BS 5467 |
| Korea and Japan | |||||||
| HFIX | 450/750 V | class 2 stranded | halogen-free (LSZH) | — | 90194 | 1.5–630 mm² | KS C 3341 |
| F-CV | 0.6/1 kV | class 2 stranded | XLPE | flame-retardant PVC | 90194 | — | KS C IEC 60502-1 |
| IV | 600 V | class 1 solid | PVC | — | 60140 | — | JIS C 3307 |
| VVF (VA) | 600 V | class 1 solid | PVC | PVC | 60140 | 1.6, 2.0, 2.6 mm solid | JIS C 3342 |
| CV | 600 V | class 2 stranded | XLPE | PVC | 90194 | — | JIS C 3605 |
| VCTF | 300 V | class 5 flexible | PVC | PVC | 60140 | — | JIS C 3306 |
No exact match. The nearest sizes:
How to read a HAR code
The designation follows CENELEC HD 361. 1st letter: H = harmonised type, A = recognised national type, N = national standard (German types start with N: NYM, NYY). Digits: rated voltage U0/U: 03 = 300/300 V, 05 = 300/500 V, 07 = 450/750 V.
Material letters, insulation first, then sheath: V = PVC, V2 = heat-resistant PVC (90 °C), V3 = PVC for low temperatures, V5 = oil-resistant PVC, R = rubber, B = EPR, N = polychloroprene (neoprene), S = silicone rubber, Z / Z1 = halogen-free polyolefin compounds, Q = polyurethane, T = textile braid. H after the materials = flat separable construction, H2 = flat non-separable.
After the dash, the conductor: U = solid (class 1), R = stranded (class 2), K = flexible for fixed installation (class 5), F = flexible for cords (class 5), H = highly flexible (class 6), Y = tinsel. Core count and size: G = includes a green-yellow protective core, X = no green-yellow core. 3G1.5 = three cores of 1.5 mm², one of them green-yellow; 4X2.5 = four cores of 2.5 mm², none green-yellow.
German national types use similar letters in a different order: N = standard type, Y = PVC, 2X = XLPE, H = halogen-free, M = sheathed installation cable, C = concentric screen, -J = with green-yellow core, -O = without. So NYY-J is a national, PVC-insulated, PVC-sheathed cable with a green-yellow core; N2XH-J is XLPE-insulated, halogen-free sheathed.
About IEC Cable Types
The table lists the harmonised types sold everywhere in Europe and the national cable types that do most of the fixed wiring work in Germany, the UK, Korea and Japan. Voltage is written U0/U: conductor-to-earth / conductor-to-conductor. A 300/500 V cord (H05…) is fine for 230/400 V supplies; 450/750 V (H07…) is required for heavier duty and for single cores in conduit in most installation rules.
Maximum conductor temperatures: 70 °C for PVC, 60 °C for ordinary rubber (EI4) cords such as H05RR-F and H07RN-F, 90 °C for XLPE power cables (N2XH, SWA, CV, F-CV). The current a cable may carry depends on that limit and on how it is installed; see cable ampacity per IEC 60364-5-52.
Choosing a flexible cord: H03VV-F for lamps and light appliances, H05VV-F for normal household appliances, H05RR-F where the cord meets heat or abrasion, H07RN-F for anything outdoors, on building sites, or dragged across floors. PVC cords stiffen and crack in the cold and should not be used outdoors in winter; rubber/polychloroprene cords stay flexible and resist oil and weather.
Korea moved its building wire from PVC (IV, HIV) to halogen-free HFIX for indoor wiring in conduit and uses flame-retardant F-CV for power feeders. Japan uses VVF ("F cable", formerly VA) flat cable for almost all house wiring, sized by solid conductor diameter (1.6 mm for ordinary 20 A branch circuits, 2.0 mm for longer runs and heavier loads) rather than mm², IV single wires in conduit, and CV (XLPE) cable for feeders.
HAR code cheat sheet
The most common letters, in order of appearance in the code.
| Position | Code | Meaning |
|---|---|---|
| 1 | H · A · N | harmonised · recognised national · national type |
| 2 | 03 · 05 · 07 | 300/300 V · 300/500 V · 450/750 V |
| 3–4 | V · V2 · R · B · N · S · Z1 | PVC · 90 °C PVC · rubber · EPR · polychloroprene · silicone · halogen-free |
| 5 | -U · -R · -K · -F · -H | solid · stranded · flexible (fixed) · flexible (cord) · highly flexible |
| 6 | 3G1.5 · 4X2.5 | 3 cores 1.5 mm² incl. green-yellow · 4 cores 2.5 mm² without |
Core colors in harmonised cables (HD 308)
2 cores: brown, blue. 3G: green-yellow, brown, blue. 4G: green-yellow, brown, black, grey. 5G: green-yellow, blue, brown, black, grey. Cables without green-yellow (X) replace it with another color, e.g. 3X: brown, black, grey.
UK twin and earth sizes
6242Y flat twin and earth has a smaller bare circuit protective conductor (CPC): 1.0 mm² T&E has a 1.0 mm² CPC, 1.5 mm² has 1.0 mm², 2.5 mm² has 1.5 mm², 4 mm² has 1.5 mm², 6 mm² has 2.5 mm², 10 mm² has 4 mm² and 16 mm² has 6 mm². Sleeve the bare CPC green-yellow at every termination.
Questions
What does H05VV-F mean?
Harmonised (H), 300/500 V (05), PVC insulation (V), PVC sheath (V), flexible class 5 conductor for cords (-F). It is the standard round PVC appliance flex, usually 0.75 to 2.5 mm².
What is the difference between H05VV-F and H07RN-F?
H05VV-F is a 300/500 V PVC cord for indoor appliances (70 °C conductor, stiff in the cold). H07RN-F is a 450/750 V rubber-insulated, polychloroprene-sheathed cable for heavy duty, outdoor and building-site use, with better resistance to abrasion, oil, water and low temperatures.
What does G mean in 3G1.5?
G means one of the cores is green-yellow (protective earth). 3G1.5 = three 1.5 mm² cores: brown, blue and green-yellow. X instead of G means no green-yellow core.
What is the difference between H07V-U, H07V-R and H07V-K?
All are 450/750 V PVC single cores. -U has a solid conductor (class 1), -R a stranded conductor (class 2, larger sizes), -K a fine-stranded flexible conductor (class 5) for panels and conduits with bends.
Can NYM-J be buried in the ground?
No. NYM-J may be used indoors and outdoors (out of direct sunlight) but not directly in the ground. Use NYY-J (or N2XY) for direct burial, or pull the cable through a suitable duct.
What is the US equivalent of H07V-K?
There is no exact one; the closest are MTW / THHN-type stranded building wire in AWG sizes. H07V-K 1.5 mm² sits between 16 AWG (1.31 mm²) and 14 AWG (2.08 mm²). See the US cable types.
Sources
- CENELEC HD 361 S3: System for cable designation (HAR code)
- EN 50525-2-11 / -2-21 / -2-31 / -3-31: Electric cables, low voltage up to 450/750 V: flexible PVC cords, rubber cords, PVC single-core, halogen-free single-core
- DIN VDE 0250-204 (NYM), DIN VDE 0276-603 (NYY), DIN VDE 0276-604 (N2XH)
- BS 6004 (PVC cables incl. 6242Y twin & earth), BS 5467 (XLPE armoured cables 600/1000 V)
- JIS C 3307 (IV), JIS C 3342 (VVF/VVR), JIS C 3605 (CV), JIS C 3306 (VCTF)
- KS C 3341 (HFIX), KS C IEC 60502-1 (0.6/1 kV XLPE power cables)
- Lapp: Technical tables: harmonised type designations (HAR code key)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.