1/2" EMT Conduit Dimensions & Fill

Conduit Sizes · EMT: electrical metallic tubing

1/2" EMT conduit has a nominal inside diameter of 0.622 in (15.8 mm) and a total inside area of 0.304 in² (196 mm²). NEC Chapter 9 allows 0.122 in² (79 mm²) for three or more conductors (40 %), 0.094 in² (61 mm²) for two and 0.161 in² (104 mm²) for one.

IDInside diameter (nominal)
15.8 mm0.622 in0.622 in15.8 mm
ODOutside diameter
17.9 mm0.706 in0.706 in17.9 mm
A₄₀Fill area, over 2 wires (40 %)
79 mm²0.122 in²0.122 in²79 mm²

Drawing

40 % fill areaID ⌀15.8 mmID ⌀0.622 inOD ⌀17.9 mmOD ⌀0.706 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

1/2" EMT specifications

Metric designator16
ODOutside diameter0.706 in17.9 mm
IDInside diameter (nominal)0.622 in15.8 mm
ATotal inside area (100 %)0.304 in²196 mm²
A₄₀Fill area, over 2 wires (40 %)0.122 in²79 mm²
A₃₁Fill area, 2 wires (31 %)0.094 in²61 mm²
A₅₃Fill area, 1 wire (53 %)0.161 in²104 mm²

Holds up to 9 × 12 AWG or 12 × 14 AWG THHN at 40 % fill (NEC Annex C).

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.