1/2" ENT Conduit Dimensions & Fill

Conduit Sizes · ENT: electrical nonmetallic tubing

1/2" ENT conduit has a nominal inside diameter of 0.560 in (14.2 mm) and a total inside area of 0.246 in² (159 mm²). NEC Chapter 9 allows 0.098 in² (63 mm²) for three or more conductors (40 %), 0.076 in² (49 mm²) for two and 0.130 in² (84 mm²) for one.

IDInside diameter (nominal)
14.2 mm0.560 in0.560 in14.2 mm
A₄₀Fill area, over 2 wires (40 %)
63 mm²0.098 in²0.098 in²63 mm²

Drawing

40 % fill areaID ⌀14.2 mmID ⌀0.560 in
Bore and 40 % fill area to scale; the wall is drawn nominally because ENT/FMC outside diameters vary by maker.Proportions shown, not to scale · Dimensions in mmDimensions in inches

1/2" ENT specifications

Metric designator16
IDInside diameter (nominal)0.560 in14.2 mm
ATotal inside area (100 %)0.246 in²159 mm²
A₄₀Fill area, over 2 wires (40 %)0.098 in²63 mm²
A₃₁Fill area, 2 wires (31 %)0.076 in²49 mm²
A₅₃Fill area, 1 wire (53 %)0.130 in²84 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.