1/2" PVC Sch 80 Conduit Dimensions & Fill

Conduit Sizes · PVC Schedule 80

1/2" PVC Sch 80 conduit has a nominal inside diameter of 0.526 in (13.4 mm) and a total inside area of 0.217 in² (140 mm²). NEC Chapter 9 allows 0.087 in² (56 mm²) for three or more conductors (40 %), 0.067 in² (43 mm²) for two and 0.115 in² (74 mm²) for one.

IDInside diameter (nominal)
13.4 mm0.526 in0.526 in13.4 mm
ODOutside diameter
21.3 mm0.840 in0.840 in21.3 mm
A₄₀Fill area, over 2 wires (40 %)
56 mm²0.087 in²0.087 in²56 mm²

Drawing

40 % fill areaID ⌀13.4 mmID ⌀0.526 inOD ⌀21.3 mmOD ⌀0.840 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

1/2" PVC Sch 80 specifications

Metric designator16
ODOutside diameter0.840 in21.3 mm
IDInside diameter (nominal)0.526 in13.4 mm
ATotal inside area (100 %)0.217 in²140 mm²
A₄₀Fill area, over 2 wires (40 %)0.087 in²56 mm²
A₃₁Fill area, 2 wires (31 %)0.067 in²43 mm²
A₅₃Fill area, 1 wire (53 %)0.115 in²74 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.