Ethernet Cable Categories: Cat5e, Cat6, Cat6A, Cat7, Cat8

Twisted-pair cable categories from Cat3 to Cat8.2. The practical summary: Cat5e runs 1 Gbit/s (and 2.5 Gbit/s) over 100 m, Cat6 10 Gbit/s only to about 55 m, Cat6A 10 Gbit/s over the full 100 m, and Cat8 25/40 Gbit/s but only over 30 m channels inside data centres.

9 categoriesChecked 2026-11-155 sources
T568A12345678T568B12345678pin 1 is on the left with the contacts facing you and the latch down
Plug viewed from the contact side, latch underneath. Only the orange and green pairs swap between the two schemes.

Category comparisonTap a category for its specs and cross-section

9 of 9
CategoryBandwidthMHzMax. speed (full channel)Channel lengthmft10GBASE-T reachmftISO/IEC 11801 classTypical conductorTypical shielding
Cat31610 Mbit/s100328—Class C22–24 AWGU/UTP
Cat5100100 Mbit/s100328—Class D (1995)22–24 AWGU/UTP
Cat5e1002.5 Gbit/s100328—Class D22–24 AWGU/UTP, F/UTP
Cat62505 Gbit/s10032855180Class E22–24 AWGU/UTP, F/UTP
Cat6A50010 Gbit/s100328100328Class EA22–24 AWGU/UTP, F/UTP, U/FTP, S/FTP
Cat760010 Gbit/s100328100328Class F22–24 AWGS/FTP
Cat7A100010 Gbit/s100328100328Class FA22–24 AWGS/FTP
Cat8 / Cat8.1200040 Gbit/s3098—Class I (Cat 8.1)22–24 AWGU/FTP, F/UTP
Cat8.2200040 Gbit/s3098—Class II (Cat 8.2)22–24 AWGF/FTP, S/FTP

Reading category, class and shielding codes

Category (TIA, North America) and class (ISO/IEC 11801, international) describe the same thing for a complete link: Cat5e ≈ Class D, Cat6 ≈ Class E, Cat6A ≈ Class EA, Cat8 ≈ Class I. Cat7 (Class F) and Cat7A (Class FA) exist only in ISO and need special connectors (GG45, TERA, ARJ45) to deliver their rating; with ordinary RJ45 plugs a "Cat7" cable performs as Cat6A.

The bandwidth in MHz is the frequency up to which the cable's loss and crosstalk are specified. It is not the data rate: 1000BASE-T moves 1 Gbit/s inside 100 MHz by using all four pairs in both directions with multi-level coding.

Shielding codes (ISO/IEC 11801 notation) have the form X/YTP: the letters before the slash are the overall screen, the letter before TP is the screen around each pair. U = unshielded, F = foil, S = braid, SF = braid plus foil. So U/UTP has no shield at all, F/UTP an overall foil, U/FTP foil on each pair, S/FTP an overall braid plus foil on each pair. Older names such as "STP" and "FTP" are ambiguous; ask for the code.

Channel length is the total of the 90 m permanent link plus up to 10 m of patch cords (100 m), or for Cat8 a 24 m link plus cords (30 m). Stranded patch cable has more loss than solid cable, so long runs should be solid-core.

About Ethernet Cable Categories

All categories use four twisted pairs and, except Cat7/7A/8.2, the familiar RJ45 (8P8C) connector, and all higher categories are backwards compatible: a Cat6A link carries 100 Mbit/s and 1 Gbit/s equipment without problems. The speed column gives the fastest IEEE 802.3 BASE-T standard the category supports over its full channel length.

For new building wiring the usual choice today is Cat6A: it supports 10GBASE-T to every outlet, handles the heat of 90 W PoE++ (IEEE 802.3bt) bundles better thanks to its larger conductors, and Wi-Fi 6/7 access points already need 2.5 or 5 Gbit/s uplinks. Cat6 is still fine for desks that will stay at 1 Gbit/s, and Cat5e for anything that never needs more than 1–2.5 Gbit/s.

Installation cable uses solid copper conductors of 22 to 24 AWG (ANSI/TIA-568; 26 AWG is allowed for shorter cords). Shielding is a product choice, not set by the category. Shielded cable only works if the shield is bonded through shielded jacks and patch panels to earth; a half-shielded installation can be worse than plain U/UTP.

Beware of copper-clad aluminium (CCA) cable sold as "Cat6": it does not meet the TIA/ISO conductor requirements, has about 60 % higher resistance, heats more with PoE and breaks more easily. Genuine category cable is solid or stranded copper and printed with the category and a listing (e.g. CMR, CMP, or EN 50575 CPR class).

T568A and T568B pin assignments

Both schemes are electrically identical; only pairs 2 (orange) and 3 (green) swap places. Use the same scheme at both ends for a straight-through cable. T568B is most common in commercial cabling in the US, T568A is the TIA preference and required by some government and residential specifications. A cable with A at one end and B at the other is a crossover cable, unnecessary for modern Auto-MDI-X equipment.

PinT568AT568B10/100BASE-T1000BASE-T and faster
1white/greenwhite/orangeTX+BI_DA+
2greenorangeTX−BI_DA−
3white/orangewhite/greenRX+BI_DB+
4blueblue—BI_DC+
5white/bluewhite/blue—BI_DC−
6orangegreenRX−BI_DB−
7white/brownwhite/brown—BI_DD+
8brownbrown—BI_DD−

Shielding codes at a glance

Overall screen / pair screen.

CodeOverall screenPair screenOld names
U/UTPnonenoneUTP
F/UTPfoilnoneFTP, ScTP
U/FTPnonefoilSTP (pair-shielded)
S/FTPbraidfoilPiMF, SSTP
SF/UTPbraid + foilnoneS-FTP

Questions

What is the difference between Cat5e, Cat6 and Cat6A?

Bandwidth and reach at 10 Gbit/s. Cat5e: 100 MHz, 1 and 2.5 Gbit/s over 100 m. Cat6: 250 MHz, 1–5 Gbit/s over 100 m, 10 Gbit/s only up to about 55 m. Cat6A: 500 MHz, 10 Gbit/s over the full 100 m.

How long can an Ethernet cable be?

100 m (328 ft) per channel for Cat5e, Cat6 and Cat6A: a 90 m permanent link plus up to 10 m of patch cords. Cat8 channels are limited to 30 m. Beyond that you need a switch, a media converter to fibre, or an extender.

Is Cat7 better than Cat6A?

On paper (600 vs 500 MHz), but in practice no: Cat7 is not a TIA category, needs GG45/TERA connectors to reach its rating, and with RJ45 plugs it is certified as Cat6A. Both carry 10 Gbit/s over 100 m.

Should I use T568A or T568B?

Either, as long as both ends of every cable and the whole installation use the same scheme. They perform identically; T568B is more common in US commercial work, T568A in residential and government specifications.

What does U/FTP or S/FTP mean?

The letters before the slash describe the overall screen, the letters before TP the screen around each pair. U/FTP = no overall screen, foil around each pair; S/FTP = overall braid plus foil around each pair; U/UTP = no shielding at all.

What AWG is Cat6 cable?

ANSI/TIA-568 requires solid installation cable of 22 to 24 AWG and allows 26 AWG for shorter cords; Cat6 products range from 22 to 26 AWG. Thin 26 AWG patch cords are meant for short lengths only.

Sources

  1. ANSI/TIA-568.2-D: Balanced Twisted-Pair Telecommunications Cabling and Components Standard (Categories 3, 5e, 6, 6A, 8)
  2. ISO/IEC 11801-1:2017, Information technology, generic cabling for customer premises (classes D, E, EA, F, FA, I, II; shield naming Annex)
  3. IEEE 802.3: 10BASE-T, 100BASE-TX, 1000BASE-T, 2.5G/5GBASE-T (802.3bz), 10GBASE-T (802.3an), 25G/40GBASE-T (802.3bq)
  4. TIA TSB-155: Guidelines for the assessment of installed Category 6 cabling to support 10GBASE-T (up to 55 m)
  5. ANSI/TIA-568.0 / 568.1: T568A and T568B pin/pair assignments

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.