1 mm² Wire: Resistance, Diameter, AWG

Metric Wire Sizes

A 1 mm² copper conductor (IEC 60228) may have at most 18.1 Ω/km (5.5169 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 19.5 Ω/km (5.9436 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 1.13 mm (0.0445 in) in diameter. The nearest AWG size is 18 AWG.

SNominal cross-section
1 mm²
RMax. resistance, class 1/2 (solid, stranded)
18.1 Ω/km5.5169 Ω/1000 ft5.5169 Ω/1000 ft18.1 Ω/km
RMax. resistance, class 5 (flexible)
19.5 Ω/km5.9436 Ω/1000 ft5.9436 Ω/1000 ft19.5 Ω/km
Nearest AWG
18 AWG

Drawing

⌀1.13 mm⌀0.0445 in1 mm²Solid round conductor, nominal area
1 mm² / 18 AWG18 AWG: 0.82 mm² (-18 %)
Left: solid round conductor of the nominal area. Right: the same with the nearest AWG / kcmil size overlaid (orange).Drawn to scale · Dimensions in mmDimensions in inches

1 mm² specifications

SNominal cross-section1 mm²
dSolid conductor diameter (calc.)1.13 mm0.0445 in
Area in kcmil1.97 kcmil
RMax. resistance, class 1/2 (solid, stranded)18.1 Ω/km5.5169 Ω/1000 ft
RMax. resistance, class 5 (flexible)19.5 Ω/km5.9436 Ω/1000 ft
Nearest AWG18 AWG
Smallest AWG with at least this area16 AWG

1 mm² is used for lighting circuits in some countries and for appliance cords up to about 10 A.

Comparable AWG sizes

All Metric Wire Sizes sizes

Compare all 19 sizes in the Metric Wire Sizes chart →

Sources

  1. IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
  2. Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
  3. Bayka: Conductor resistance (IEC 60228 / VDE 0295)
  4. ASTM B258: AWG nominal diameters and areas (for the AWG comparison)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.