NEMA Plug and Receptacle Configuration Chart
A NEMA configuration such as 14-50 or L6-30 is a code: the number before the dash fixes the voltage and the number of poles and wires, the number after it is the current rating in amps, and a leading L means a locking (twist-lock) device. A 14-50 is therefore 125/250 V, 3 poles, 4 wires, 50 A.
NEMA configurationsTap a configuration for its contacts and ratings
| Config | Rated voltage | Rated currentA | Poles | Wires | Grounding | Typical use |
|---|---|---|---|---|---|---|
| Straight blade | ||||||
| 1-15 | 125 V | 15 | 2 | 2 | Non-grounding | Old two-prong outlets; double-insulated small appliances |
| 5-15 | 125 V | 15 | 2 | 3 | Grounding | Standard US/Canadian household outlet |
| 5-20 | 125 V | 20 | 2 | 3 | Grounding | Kitchen, garage and commercial 20 A circuits; T-slot receptacle also takes 5-15 plugs |
| 5-30 | 125 V | 30 | 2 | 3 | Grounding | Uncommon; high-current 120 V equipment |
| 5-50 | 125 V | 50 | 2 | 3 | Grounding | Uncommon; high-current 120 V equipment |
| 6-15 | 250 V | 15 | 2 | 3 | Grounding | 240 V window air conditioners, small compressors |
| 6-20 | 250 V | 20 | 2 | 3 | Grounding | 240 V air conditioners, compressors, shop machines |
| 6-30 | 250 V | 30 | 2 | 3 | Grounding | Welders, kilns, compressors, shop equipment |
| 6-50 | 250 V | 50 | 2 | 3 | Grounding | Welders, kilns, plasma cutters, Level 2 EV charging |
| 10-30 | 125/250 V | 30 | 3 | 3 | Non-grounding | Old 3-wire clothes-dryer outlets (no separate ground) |
| 10-50 | 125/250 V | 50 | 3 | 3 | Non-grounding | Old 3-wire electric-range outlets (no separate ground) |
| 14-20 | 125/250 V | 20 | 3 | 4 | Grounding | Rare; 120/240 V appliances |
| 14-30 | 125/250 V | 30 | 3 | 4 | Grounding | 4-wire clothes dryers |
| 14-50 | 125/250 V | 50 | 3 | 4 | Grounding | Electric ranges, RV 50 A pedestals, EV charging |
| 14-60 | 125/250 V | 60 | 3 | 4 | Grounding | EV chargers and other large 120/240 V loads |
| TT-30 | 125 V | 30 | 2 | 3 | Grounding | RV and travel-trailer 30 A hookups |
| Locking (twist-lock) | ||||||
| L5-15 | 125 V | 15 | 2 | 3 | Grounding | Locking 120 V equipment connections |
| L5-20 | 125 V | 20 | 2 | 3 | Grounding | Locking 120 V equipment, stage and event power |
| L5-30 | 125 V | 30 | 2 | 3 | Grounding | Marine shore power, generators, RVs, servers |
| L6-15 | 250 V | 15 | 2 | 3 | Grounding | Locking 240 V equipment |
| L6-20 | 250 V | 20 | 2 | 3 | Grounding | Data-center PDUs, 208/240 V equipment |
| L6-30 | 250 V | 30 | 2 | 3 | Grounding | Data-center PDUs, welders, generators |
| L10-30 | 125/250 V | 30 | 3 | 3 | Non-grounding | Older generators (no separate ground) |
| L14-20 | 125/250 V | 20 | 3 | 4 | Grounding | Portable generators, stage power |
| L14-30 | 125/250 V | 30 | 3 | 4 | Grounding | Portable generators and transfer-switch inlets |
| L15-20 | 3Ø 250 V | 20 | 3 | 4 | Grounding | Three-phase 240 V equipment |
| L15-30 | 3Ø 250 V | 30 | 3 | 4 | Grounding | Three-phase 240 V equipment |
| L16-20 | 3Ø 480 V | 20 | 3 | 4 | Grounding | Three-phase 480 V equipment |
| L16-30 | 3Ø 480 V | 30 | 3 | 4 | Grounding | Three-phase 480 V equipment |
| L21-20 | 3ØY 120/208 V | 20 | 4 | 5 | Grounding | Three-phase 208 V PDUs and equipment |
| L21-30 | 3ØY 120/208 V | 30 | 4 | 5 | Grounding | Three-phase 208 V data-center PDUs |
| L22-20 | 3ØY 277/480 V | 20 | 4 | 5 | Grounding | Three-phase 480 V equipment with neutral |
| L22-30 | 3ØY 277/480 V | 30 | 4 | 5 | Grounding | Three-phase 480 V equipment with neutral |
No exact match. The nearest sizes:
How to read a NEMA configuration
Prefix. No prefix means straight blades that push in. L means curved blades that lock with a quarter turn. TT (travel trailer) is a stand-alone RV configuration.
First number: the configuration. It sets voltage, poles and wires: 1 = 125 V 2-pole 2-wire; 5 = 125 V 2-pole 3-wire grounding; 6 = 250 V 2-pole 3-wire grounding; 10 = 125/250 V 3-pole 3-wire, no ground; 14 = 125/250 V 3-pole 4-wire grounding; 15 = three-phase 250 V; 16 = three-phase 480 V; 21 = three-phase wye 120/208 V 4-pole 5-wire; 22 = three-phase wye 277/480 V.
Second number: the current rating in amps: 15, 20, 30, 50 or 60. P after it means plug, R receptacle: a 6-50P goes into a 6-50R.
Poles and wires. Poles are the current-carrying contacts (hots and neutral); wires count the grounding conductor as well. "3-pole 4-wire" = two hots, a neutral and a ground. Terminal letters on the device: X, Y, Z for hots (brass screws), W for neutral (silver screw), G for ground (green screw).
Each configuration is keyed so that a plug cannot enter a receptacle of a different voltage or a lower current rating. The one deliberate exception: a 20 A T-slot receptacle (5-20R, 6-20R) also accepts the 15 A plug of the same series.
About NEMA Configurations
ANSI/NEMA WD 6 is the North American standard that defines the shape of general-purpose plugs and receptacles up to 60 A. Every configuration on this page has a fixed blade pattern; two devices with the same configuration number are interchangeable whichever brand made them.
In a house you meet only a few of them: 5-15 and 5-20 for 120 V outlets, 6-20/6-30/6-50 for 240 V tools and welders, 14-30 for the dryer and 14-50 for the range, RV pedestal or EV charger. The L (twist-lock) devices are for equipment that must not come unplugged by accident: generators (L14-30), data-center power strips (L6-30, L21-30) and marine shore power (L5-30).
The rating on the receptacle has to suit the circuit. Under NEC Table 210.21(B)(3) a 15 A circuit may have only 15 A receptacles; a 20 A circuit with more than one outlet may have 15 A or 20 A receptacles; 30, 40 and 50 A circuits need receptacles of the same rating (40 A circuits use 50 A receptacles). Common copper wire sizes are 14 AWG for 15 A, 12 AWG for 20 A and 10 AWG for 30 A; 50 A and 60 A circuits depend on cable type and terminal temperature rating, so check NEC 310.16 for the run.
The contact drawing on each page shows which contacts the configuration has and how they are grouped. It is a schematic: the real blades are keyed by width, angle and shape, and WD 6 dimensions are not reproduced here.
Configuration numbers at a glance
The same configuration number is used for straight-blade and locking devices with the same electrical rating: a 14-30 and an L14-30 are both 125/250 V 3-pole 4-wire 30 A, but their blades are completely different.
| Config | Voltage | Poles / wires | Ground | Straight | Locking |
|---|---|---|---|---|---|
| 1 | 125 V | 2P 2W | No | 1-15 | L1-15 |
| 5 | 125 V | 2P 3W | Yes | 5-15, 5-20, 5-30, 5-50 | L5-15, L5-20, L5-30 |
| 6 | 250 V | 2P 3W | Yes | 6-15, 6-20, 6-30, 6-50 | L6-15, L6-20, L6-30 |
| 7 | 277 V AC | 2P 3W | Yes | 7-15 … 7-50 | L7-15 … L7-30 |
| 10 | 125/250 V | 3P 3W | No | 10-30, 10-50 | L10-20, L10-30 |
| 14 | 125/250 V | 3P 4W | Yes | 14-15 … 14-60 | L14-20, L14-30 |
| 15 | 3Ø 250 V | 3P 4W | Yes | 15-15 … 15-60 | L15-20, L15-30 |
| 16 | 3Ø 480 V | 3P 4W | Yes | — | L16-20, L16-30 |
| 21 | 3ØY 120/208 V | 4P 5W | Yes | — | L21-20, L21-30 |
| 22 | 3ØY 277/480 V | 4P 5W | Yes | — | L22-20, L22-30 |
| TT | 125 V | 2P 3W | Yes | TT-30 | — |
Telling the common straight-blade outlets apart
5-15R: two parallel vertical slots, the neutral slot (left, when the ground hole is at the bottom) taller than the hot slot, and a round/D-shaped ground hole. 5-20R: the neutral slot is a sideways T, so it takes both the vertical 15 A blade and the horizontal 20 A blade.
6-15R: both slots horizontal, in line. 6-20R: one horizontal slot and one T-slot, so it accepts 6-15 and 6-20 plugs. A 6-series outlet has no neutral: it feeds a 240 V load from two hots.
TT-30R: two angled slots, each 45° from vertical and 90° to each other, plus a round ground hole. A 10-30 looks similar but its blades are at 30° and 60°. TT-30 is 120 V only. Plugging a 240 V appliance into a miswired TT-30 pedestal is a classic way to destroy RV electronics.
30 A and 50 A outlets are larger, with 1 in (25.4 mm) between the power slots on 5-30 and 5-50. The 30 A versions are keyed by an L-shaped neutral (5-30, 14-30); the 14-50 has a straight neutral sized so it does not mate with a 14-30; 5-50 and 6-50 look like bigger versions of the 5-15. Read the configuration number printed on the face of the receptacle rather than identifying by eye.
Three-wire versus four-wire dryers and ranges
Until the 1996 NEC, dryers and ranges could be fed by 3-wire 10-30 and 10-50 receptacles, with the appliance frame bonded to the neutral. New installations must be 4-wire (14-30, 14-50) with a separate equipment ground (NEC 250.140). An existing 3-wire circuit may stay; when you replace it or move the appliance, change the cord to match the receptacle, never the other way round with an adapter.
EV charging on a receptacle
EV charging is a continuous load, so it may draw only 80 % of the circuit rating: 40 A on a 50 A circuit (14-50 or 6-50), 24 A on a 30 A circuit, 16 A on a 20 A circuit. Since the 2020 NEC, 125 V and 250 V receptacles in garages need GFCI protection (210.8(A)), which some portable chargers trip; a hard-wired charger avoids this.
Questions
What is the difference between NEMA 14-50 and 6-50?
Both are 50 A 240 V outlets. A 14-50 has four contacts (two hots, neutral, ground) and also supplies 120 V; a 6-50 has three (two hots, ground) and supplies 240 V only. An EV charger that needs only 240 V can use either; an RV or range needs the 14-50.
Can I plug a 15 A plug into a 20 A outlet?
Yes, for the same voltage series. A 5-20R and a 6-20R have a T-slot that accepts the 15 A plug (5-15P or 6-15P). The reverse does not work: a 20 A plug has a horizontal blade that will not enter a 15 A receptacle.
What outlet does a dryer use?
New dryer circuits use a NEMA 14-30 (4-wire, 30 A, 125/250 V). Older homes often have a 10-30 (3-wire, no separate ground). Change the dryer cord to match the outlet; the cords are sold as 3-wire and 4-wire kits.
What plug does a portable generator use?
Most 5–10 kW portable generators have an L14-30R (120/240 V, 30 A, 7,200 VA) for a transfer switch or inlet, plus 5-20R outlets. Larger units add a 14-50R; smaller ones an L5-30R (120 V, 30 A).
Is an RV 30 A plug 120 V or 240 V?
The RV 30 A plug, TT-30, is 120 V (3,600 VA). The RV 50 A plug is a 14-50, which carries two 120 V legs that make 240 V between them.
What does the L in L14-30 mean?
Locking. The blades are curved; you push the plug in and turn it about a quarter turn clockwise to lock. An L14-30 has the same rating as a straight-blade 14-30 (125/250 V, 30 A, 4-wire) but the two do not fit each other.
Sources
- ANSI/NEMA WD 6: Wiring Devices: Dimensional Specifications (configuration chart)
- Hubbell Wiring Device-Kellems: NEMA configuration chart (straight blade and Twist-Lock)
- Leviton: NEMA configuration chart
- Legrand / Pass & Seymour: NEMA configurations for plugs and receptacles
- NFPA 70 (NEC) 406.4, 210.21(B)(3): receptacle ratings on branch circuits
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.