2" EMT Conduit Dimensions & Fill

Conduit Sizes · EMT: electrical metallic tubing

2" EMT conduit has a nominal inside diameter of 2.067 in (52.5 mm) and a total inside area of 3.356 in² (2,165 mm²). NEC Chapter 9 allows 1.342 in² (866 mm²) for three or more conductors (40 %), 1.040 in² (671 mm²) for two and 1.779 in² (1148 mm²) for one.

IDInside diameter (nominal)
52.5 mm2.067 in2.067 in52.5 mm
ODOutside diameter
55.8 mm2.197 in2.197 in55.8 mm
A₄₀Fill area, over 2 wires (40 %)
866 mm²1.342 in²1.342 in²866 mm²

Drawing

40 % fill areaID ⌀52.5 mmID ⌀2.067 inOD ⌀55.8 mmOD ⌀2.197 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

2" EMT specifications

Metric designator53
ODOutside diameter2.197 in55.8 mm
IDInside diameter (nominal)2.067 in52.5 mm
ATotal inside area (100 %)3.356 in²2,165 mm²
A₄₀Fill area, over 2 wires (40 %)1.342 in²866 mm²
A₃₁Fill area, 2 wires (31 %)1.040 in²671 mm²
A₅₃Fill area, 1 wire (53 %)1.779 in²1148 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.