2" PVC Sch 40 Conduit Dimensions & Fill
Conduit Sizes · PVC Schedule 40
2" PVC Sch 40 conduit has a nominal inside diameter of 2.047 in (52.0 mm) and a total inside area of 3.291 in² (2,123 mm²). NEC Chapter 9 allows 1.316 in² (849 mm²) for three or more conductors (40 %), 1.020 in² (658 mm²) for two and 1.744 in² (1125 mm²) for one.
- IDInside diameter (nominal)
- 52.0 mm2.047 in2.047 in52.0 mm
- ODOutside diameter
- 60.3 mm2.375 in2.375 in60.3 mm
- A₄₀Fill area, over 2 wires (40 %)
- 849 mm²1.316 in²1.316 in²849 mm²
Drawing
2" PVC Sch 40 specifications
| Metric designator | 53 |
|---|---|
| ODOutside diameter | 2.375 in60.3 mm |
| IDInside diameter (nominal) | 2.047 in52.0 mm |
| ATotal inside area (100 %) | 3.291 in²2,123 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 1.316 in²849 mm² |
| A₃₁Fill area, 2 wires (31 %) | 1.020 in²658 mm² |
| A₅₃Fill area, 1 wire (53 %) | 1.744 in²1125 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.