2" FMC Conduit Dimensions & Fill

Conduit Sizes · FMC: flexible metal conduit

2" FMC conduit has a nominal inside diameter of 2.040 in (51.8 mm) and a total inside area of 3.269 in² (2,109 mm²). NEC Chapter 9 allows 1.308 in² (844 mm²) for three or more conductors (40 %), 1.013 in² (654 mm²) for two and 1.733 in² (1118 mm²) for one.

IDInside diameter (nominal)
51.8 mm2.040 in2.040 in51.8 mm
A₄₀Fill area, over 2 wires (40 %)
844 mm²1.308 in²1.308 in²844 mm²

Drawing

40 % fill areaID ⌀51.8 mmID ⌀2.040 in
Bore and 40 % fill area to scale; the wall is drawn nominally because ENT/FMC outside diameters vary by maker.Proportions shown, not to scale · Dimensions in mmDimensions in inches

2" FMC specifications

Metric designator53
IDInside diameter (nominal)2.040 in51.8 mm
ATotal inside area (100 %)3.269 in²2,109 mm²
A₄₀Fill area, over 2 wires (40 %)1.308 in²844 mm²
A₃₁Fill area, 2 wires (31 %)1.013 in²654 mm²
A₅₃Fill area, 1 wire (53 %)1.733 in²1118 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.