2" RMC Conduit Dimensions & Fill

Conduit Sizes · RMC: rigid metal conduit (GRC)

2" RMC conduit has a nominal inside diameter of 2.083 in (52.9 mm) and a total inside area of 3.408 in² (2,199 mm²). NEC Chapter 9 allows 1.363 in² (879 mm²) for three or more conductors (40 %), 1.056 in² (681 mm²) for two and 1.806 in² (1165 mm²) for one.

IDInside diameter (nominal)
52.9 mm2.083 in2.083 in52.9 mm
ODOutside diameter
60.3 mm2.375 in2.375 in60.3 mm
A₄₀Fill area, over 2 wires (40 %)
879 mm²1.363 in²1.363 in²879 mm²

Drawing

40 % fill areaID ⌀52.9 mmID ⌀2.083 inOD ⌀60.3 mmOD ⌀2.375 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

2" RMC specifications

Metric designator53
ODOutside diameter2.375 in60.3 mm
IDInside diameter (nominal)2.083 in52.9 mm
ATotal inside area (100 %)3.408 in²2,199 mm²
A₄₀Fill area, over 2 wires (40 %)1.363 in²879 mm²
A₃₁Fill area, 2 wires (31 %)1.056 in²681 mm²
A₅₃Fill area, 1 wire (53 %)1.806 in²1165 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.