2" IMC Conduit Dimensions & Fill

Conduit Sizes · IMC: intermediate metal conduit

2" IMC conduit has a nominal inside diameter of 2.150 in (54.6 mm) and a total inside area of 3.630 in² (2,342 mm²). NEC Chapter 9 allows 1.452 in² (937 mm²) for three or more conductors (40 %), 1.125 in² (726 mm²) for two and 1.924 in² (1241 mm²) for one.

IDInside diameter (nominal)
54.6 mm2.150 in2.150 in54.6 mm
ODOutside diameter
59.9 mm2.360 in2.360 in59.9 mm
A₄₀Fill area, over 2 wires (40 %)
937 mm²1.452 in²1.452 in²937 mm²

Drawing

40 % fill areaID ⌀54.6 mmID ⌀2.150 inOD ⌀59.9 mmOD ⌀2.360 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

2" IMC specifications

Metric designator53
ODOutside diameter2.360 in59.9 mm
IDInside diameter (nominal)2.150 in54.6 mm
ATotal inside area (100 %)3.630 in²2,342 mm²
A₄₀Fill area, over 2 wires (40 %)1.452 in²937 mm²
A₃₁Fill area, 2 wires (31 %)1.125 in²726 mm²
A₅₃Fill area, 1 wire (53 %)1.924 in²1241 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.