2" PVC Sch 80 Conduit Dimensions & Fill
Conduit Sizes · PVC Schedule 80
2" PVC Sch 80 conduit has a nominal inside diameter of 1.913 in (48.6 mm) and a total inside area of 2.874 in² (1,854 mm²). NEC Chapter 9 allows 1.150 in² (742 mm²) for three or more conductors (40 %), 0.891 in² (575 mm²) for two and 1.523 in² (983 mm²) for one.
- IDInside diameter (nominal)
- 48.6 mm1.913 in1.913 in48.6 mm
- ODOutside diameter
- 60.3 mm2.375 in2.375 in60.3 mm
- A₄₀Fill area, over 2 wires (40 %)
- 742 mm²1.150 in²1.150 in²742 mm²
Drawing
2" PVC Sch 80 specifications
| Metric designator | 53 |
|---|---|
| ODOutside diameter | 2.375 in60.3 mm |
| IDInside diameter (nominal) | 1.913 in48.6 mm |
| ATotal inside area (100 %) | 2.874 in²1,854 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 1.150 in²742 mm² |
| A₃₁Fill area, 2 wires (31 %) | 0.891 in²575 mm² |
| A₅₃Fill area, 1 wire (53 %) | 1.523 in²983 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.