IEC 60309 Industrial Plug Chart: Colours, Clock Positions, 16/32/63/125 A
IEC 60309 industrial plugs ("CEE", "commando", "pin and sleeve") are coded twice: the colour gives the voltage band (yellow 110 V, blue 230 V, red 400 V) and the clock position of the earth pin, read with the keyway at 6 o'clock, keys plugs of the same size and colour to one supply. The common blue caravan plug is 16 A 2P+E 230 V, earth at 6h.
IEC 60309 plugsTap a plug for its socket face and ratings
| Plug | Colour | Rated currentA | Poles | Voltage band | Earth position | dLine/neutral pin diametermmin | Typical use |
|---|---|---|---|---|---|---|---|
| Blue: 200–250 V | |||||||
| 16 A 2P+E 6h | #1F5FBF | 16 | 2P+E | 200–250 V | 6h | 50.197 | Single-phase 230 V: caravans, campsites, marine, outdoor events |
| 32 A 2P+E 6h | #1F5FBF | 32 | 2P+E | 200–250 V | 6h | 60.236 | Single-phase 230 V: EV charging, generators, stage power |
| 63 A 2P+E 6h | #1F5FBF | 63 | 2P+E | 200–250 V | 6h | — | Single-phase 230 V high-current supplies |
| 125 A 2P+E 6h | #1F5FBF | 125 | 2P+E | 200–250 V | 6h | — | Single-phase 230 V large supplies |
| 16 A 3P+E 9h | #1F5FBF | 16 | 3P+E | 200–250 V | 9h | 50.197 | Three-phase 230 V delta systems (e.g. Norway IT networks) |
| 32 A 3P+E 9h | #1F5FBF | 32 | 3P+E | 200–250 V | 9h | 60.236 | Three-phase 230 V delta systems |
| 16 A 3P+N+E 9h | #1F5FBF | 16 | 3P+N+E | 120/208–144/250 V | 9h | 50.197 | North American three-phase wye 120/208 V (rated 20 A under UL) |
| 32 A 3P+N+E 9h | #1F5FBF | 32 | 3P+N+E | 120/208–144/250 V | 9h | 60.236 | North American 120/208 V wye: data-center PDUs (rated 30 A under UL) |
| Red: 380–480 V | |||||||
| 16 A 2P+E 9h | #D8261F | 16 | 2P+E | 380–415 V | 9h | 50.197 | Two-phase 400 V loads (welders) without neutral |
| 32 A 2P+E 9h | #D8261F | 32 | 2P+E | 380–415 V | 9h | 60.236 | Two-phase 400 V loads (welders) without neutral |
| 16 A 3P+E 6h | #D8261F | 16 | 3P+E | 380–415 V | 6h | 50.197 | Three-phase 400 V motors and machines without neutral |
| 32 A 3P+E 6h | #D8261F | 32 | 3P+E | 380–415 V | 6h | 60.236 | Three-phase 400 V motors, compressors, machines |
| 63 A 3P+E 6h | #D8261F | 63 | 3P+E | 380–415 V | 6h | — | Three-phase 400 V large machines |
| 125 A 3P+E 6h | #D8261F | 125 | 3P+E | 380–415 V | 6h | — | Three-phase 400 V large machines |
| 16 A 3P+N+E 6h | #D8261F | 16 | 3P+N+E | 200/346–240/415 V | 6h | 50.197 | Three-phase 400 V with neutral: workshops, kitchens, EV chargers |
| 32 A 3P+N+E 6h | #D8261F | 32 | 3P+N+E | 200/346–240/415 V | 6h | 60.236 | Three-phase 400 V with neutral: EV chargers, events, site power |
| 63 A 3P+N+E 6h | #D8261F | 63 | 3P+N+E | 200/346–240/415 V | 6h | — | Three-phase 400 V distribution, events |
| 125 A 3P+N+E 6h | #D8261F | 125 | 3P+N+E | 200/346–240/415 V | 6h | — | Three-phase 400 V main event and site distribution |
| 16 A 3P+N+E 7h | #D8261F | 16 | 3P+N+E | 277/480 V | 7h | 50.197 | North American 277/480 V wye (rated 20 A under UL) |
| 32 A 3P+N+E 7h | #D8261F | 32 | 3P+N+E | 277/480 V | 7h | 60.236 | North American 277/480 V wye (rated 30 A under UL) |
| Yellow: 100–130 V | |||||||
| 16 A 2P+E 4h | #F4CF1A | 16 | 2P+E | 100–130 V | 4h | 50.197 | UK 110 V centre-tapped site supplies for power tools |
| 32 A 2P+E 4h | #F4CF1A | 32 | 2P+E | 100–130 V | 4h | 60.236 | UK 110 V site supplies: heavier tools, transformers |
| Black: 500–690 V | |||||||
| 32 A 3P+N+E 5h | #1B1B1B | 32 | 3P+N+E | 347/600 V | 5h | 60.236 | Canadian 347/600 V wye systems |
No exact match. The nearest sizes:
How to identify an IEC 60309 plug
1. Colour = voltage band (50/60 Hz): violet 20–25 V, white 40–50 V, yellow 100–130 V, blue 200–250 V, red 380–480 V, black 500–690 V. Green marks 60–500 Hz supplies (aircraft ground power, high-frequency tools); grey is used for voltages that have no colour of their own.
2. Number of contacts. 3 pins = 2P+E (single phase: L, N, earth). 4 pins = 3P+E (three phases, earth, no neutral). 5 pins = 3P+N+E (three phases, neutral, earth).
3. Clock position. Look into the socket (or at the plug's pins from the front) with the large keyway at the bottom, at 6 o'clock. The earth contact is the largest pin; the hour it points to is the earth position. A 2P+E at 6h is 230 V, at 4h 110 V, at 9h 400 V. Looking into the socket, the other contacts follow the earth clockwise: L, N (2P+E); L1, L2, L3 (3P+E); L1, L2, L3, N (3P+N+E).
4. Size = current. 16, 32, 63 and 125 A sizes have different diameters, so a 32 A plug cannot enter a 16 A socket. UL/CSA-listed versions of the same sizes are rated 20, 30, 60 and 100 A.
Designation. A marking such as "32 A 3P+N+E 6h 400 V IP44" contains everything: current, poles, earth position, voltage and enclosure rating.
About IEC 60309 Industrial Plugs
IEC 60309 is the international system of industrial plugs and sockets. Part 1 sets the general requirements; part 2 fixes the interchangeable dimensions. The old European name CEE 17 is still common, as are "commando" (UK, after an MK trade name) and "pin and sleeve" (North America).
The design prevents mismatches by three independent features: body diameter (current), number of pins (poles) and the angular position of the earth pin relative to the keyway (voltage and frequency). The colour repeats the voltage information so it can be read from across a building site.
Most installations need only a handful of types. In Europe: blue 16 A and 32 A 2P+E for single-phase supplies (campsites, marinas, EV chargers) and red 16 A, 32 A and 63 A 3P+N+E (5-pin) for 400 V three-phase. In the UK: yellow 16 A and 32 A 110 V 4h for site tools. In North American data centers: blue 3P+N+E 9h 120/208 V and red 7h 277/480 V pin-and-sleeve connectors.
Sockets come as splash-proof IP44 (lid with spring, typical for 16/32 A) and watertight IP67 (screw or bayonet lid and gasketed plug, required on many outdoor and wash-down sites). An IP67 plug in an IP44 socket gives only IP44.
Colours and voltage bands
| Colour | Voltage band | Typical systems |
|---|---|---|
| Violet | 20–25 V | Extra-low voltage, safety transformers |
| White | 40–50 V | Extra-low voltage (wet areas, boilers) |
| Yellow | 100–130 V | UK 110 V site supply (55-0-55 V centre tap) |
| Blue | 200–250 V | 230 V single phase; 120/208 V wye (NA); 230 V delta |
| Red | 380–480 V | 400 V three phase (230/400 V); 480 V (NA) |
| Black | 500–690 V | 600 V and 690 V systems |
| Green | >60–500 Hz | Higher-frequency supplies (e.g. 400 Hz) |
| Grey | Other | Voltages without a colour (e.g. some 277 V) |
Earth positions in common use
Positions read from the front of the socket with the keyway at 6 o'clock. These are the combinations listed consistently by manufacturers; positions for DC, isolating-transformer and special supplies (2h, 3h, 10h, 12h and others) vary between catalogues, so check the device marking. The 7h position (277/480 V) is listed as black in the IEC keying table but sold in red by most North American makers, because 480 V is the top of the red band.
| Earth | 2P+E | 3P+E | 3P+N+E |
|---|---|---|---|
| 4h | Yellow 100–130 V | Yellow 100–130 V | Yellow 57/100–75/130 V |
| 5h | — | — | Black 347/600–400/690 V |
| 6h | Blue 200–250 V | Red 380–415 V | Red 200/346–240/415 V |
| 7h | — | — | Red or black 277/480 V |
| 9h | Red 380–415 V | Blue 200–250 V | Blue 120/208–144/250 V |
Current ratings and cables
Sizes: 16 A, 32 A, 63 A and 125 A (IEC); the same sizes are listed as 20, 30, 60 and 100 A under UL 1682 / CSA in North America. A 16 A 230 V supply delivers up to 3.7 kW; 32 A single phase 7.4 kW; 16 A three-phase 400 V 11 kW; 32 A three-phase 22 kW. These are the familiar EV charger steps. Cable size depends on length, installation method and local rules; 2.5 mm² (16 A) and 6 mm² (32 A) are common for short flexible cords.
Nominal pin sizes (IEC 60309-2): line and neutral pins 5 mm in diameter for 16 A and 6 mm for 32 A, the earth pin 2 mm thicker (7 and 8 mm); 16 A pins are 37 mm long. Plugs of 63 A and 125 A may carry a shorter central pilot contact that breaks first, so a load can be switched off before the pins separate.
Questions
What does 6h mean on an industrial plug?
The earth contact sits at the 6 o'clock position when you look at the socket face with the keyway at the bottom. For a 2P+E plug, 6h means 200–250 V (blue); for 3P+E and 3P+N+E it means 380–415 V three-phase (red).
What is the difference between a 4-pin and 5-pin red plug?
A 4-pin red plug is 3P+E: three phases and earth, no neutral, for 400 V motors. A 5-pin is 3P+N+E with a neutral, so it can also supply 230 V loads between a phase and neutral. They do not fit each other.
How many kW is a 32 A blue plug?
At 230 V, 32 A × 230 V = 7.36 kW. A 32 A red 5-pin plug at 400 V three-phase gives √3 × 400 V × 32 A ≈ 22 kW; a 16 A red plug about 11 kW.
Can I use a blue caravan plug in North America?
The plug is the same IEC 60309 design, but North American RV parks use NEMA TT-30 and 14-50 receptacles, not IEC 60309. In North America blue 2P+E 6h connectors are found on 208/240 V equipment and data-center PDUs, rated 20 or 30 A.
What is the difference between IP44 and IP67 industrial sockets?
IP44 is splash-proof: a spring lid closes when nothing is plugged in. IP67 is watertight to temporary immersion: the plug screws or locks onto the socket with a gasket. Use IP67 where hoses, rain or floods can reach the connection.
Sources
- IEC 60309-1 and IEC 60309-2: Plugs, socket-outlets and couplers for industrial purposes
- Walther Electric: IEC 60309-1 & 2 pin and sleeve devices catalogue (voltage colours and clock positions)
- Palazzoli: Plugs, socket-outlets and couplers for industrial purposes: clock position
- Museum of Plugs and Sockets: IEC 60309 industrial standard
- BS 7375 / BS 7671: 110 V reduced low voltage site supplies (UK practice)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.